Release notes

For: CMe3100

CMe3100 Firmware version 1.17.X

Firmware version 1.17.2

Release date: 2026-01-16

Important:

This is a patch release to fix one smaller issue regarding logging in device.

Highlights:

-

Table 191. Implemented changes

ID Description
CME3-2796 [FIX] Problem where the system could generate unnecessary log messages in certain situations.


 

Firmware version 1.17.1

Release date: 2025-12-08

Important:

-

Highlights:

  • Functionality to send meter list from CMe3100 to connected Wireless receiver(s) to lock desired meters in receiver.
  • Improved usability when installing M-Bus meters via TCP by including the IP address and port in the meter list to neable easy batch installation.

Table 192. Implemented changes

ID Description
CME3-2775 [ADDED] Added possibility to add IP adress and port in install (meter list) when installing M-Bus meters via TCP
CME3-2773 [FIX] Insecure HTTP frame loaded over HTTPS when using reverse proxy
CME3-2716 [ADDED] Improve security handling
CME3-2697 [ADDED] Feature to synchronize meterlist to wireless M-Bus receiver
CME3-2640 [ADDED] MQTT connection timeout configurable
CME3-2632 [ADDED] Support for a configurable internet-status check in dashboard, allowing the system to determine whether the gateway is connected to the internet
CME3-2777 [FIX] Issue after setting new password on first use
CME3-2759 [FIX] Issue when reactivating adaptive retries


 

Firmware version 1.17.0

Release date: 2025-10-07

Important:

The certificate for the computer setup program “Configure CMe3100” has expired which removes the possibility to install the program on your computer. A new updated certificate is included from firmware version 1.17.0 (and later).

If you already have the setup program installed on your computer, it will continue to work as normal. However, if you need to install the program again, there are now two options:

  1. Update your gateway to firmware version 1.17.0 or newer, which includes the updated certificate and allows successful installation of the setup program. Download the firmware here: CMe3100 firmware download
  2. Download the setup program with a renewed certificate (CMe3100 setup file). This version can be installed on any computer, regardless of firmware version.

Highlights:

  • Stability improvements
  • Overall improvements of logging in device
  • Implemented new security rule at first login where the user is required to set a new password. The password must be at least 12 characters long and include at least one special character, one number, and both uppercase and lowercase letters. If the password is forgotten, the device must be restored to factory settings to regain access.

Table 193. Implemented changes

ID Description
CME3-2746 [ADDED] Add indexing to database to improve performance
CME3-2737 [ADDED] Make default meters per page 50 instead of 10
CME3-2736 [FIX] Adjust JVM flags for improved stability and logging
CME3-2735 [FIX] Fix bug in logging handling to improve stability
CME3-2733 [ADDED] Added feature to log and store information if OutOfMemory exception occurs
CME3-2732 [FIX] Make watchdog more robust
CME3-2731 [FIX] Update certificate on Windows installer file
CME3-2730 [ADDED] Option to generate http report on disk before sending to recipient
CME3-2720 [ADDED] Smart log-cleaning to maintain log-database size and information
CME3-2718 [ADDED] Force user to set secure password before first use of device
CME3-2717 [ADDED] Improved debug-logging when sending HTTP reports
CME3-2686 [ADDED] Display warning if there are passive meters present
CME3-2655 [ADDED] Helpttext clarification on SFTP report
CME3-2414 [ADDED] Updated list of manufacturers when adding decryption keys
CME3-2359 [ADDED] New log-level added for fine debug logging
CME3-2729 [FIX] UI error for footer on meter page


 

CMe3100 Older Firmware versions

CMe3100 Firmware version 1.16.X
Firmware version 1.16.1

Release date: 2025-08-29

Important:

This patch release is only relevant for users who is utilizing MQTT push reports. If you need further information before upgrading, please contact Elvaco Support.

Highlights:

  • Bug fix release for MQTT push reports

Table 194. Implemented changes

ID Description
CME3-2715 [FIX] The MQTT report sender failed to initialize SSL context due to a missing KeyManager, causing TLS handshake failures and preventing secure MQTT connections


 

Firmware version 1.16.0

Release date: 2025-07-07

Important:

If you need further information before upgrading, please contact Elvaco Support.

Highlights:

  • Added support for sending decrypted data virtually over TCP or Slave port
  • Enabled more report templates using MQTT push reports
  • Improved usability when using CMe3100 with CMeX50 or CMi Box (CMi5110)

Table 195. Implemented changes

ID Description
CME3-2354 Added support for sending decrypted data virtually over TCP and Slave ports
CME3-2674 Enabled import of meter lists along with associated keys in a single file
CME3-2662 Added wireless M-Bus receiver information in installation report
CME3-2551 Fixed issue with SFTP push report when using username/password authentication
CME3-2672 Existing report templates should be available for MQTT
CME3-2638 Added log information regarding MQTT Push report success event
CME3-2637 Fixed email push report 1107 Energy Consumption
CME3-2683 Default BACnet object name should only contain alphanumeric characters
CME3-2682 Added activate/deactivate selected BACnet objects in BACnet mapping page in GUI, similar to modbus mapping page
CME3-2678 Fixed issue with BACnet object naming
CME3-2636 Various minor improvements and stability enhancements
Added functions for sending M-Bus commands to an Elvaco wireless M-Bus receiver
CME3-2661 Merge meter list and key list UI's into a single meter list page
CME3-2660 Clear selected meter(s) and associated keys in wireless M-Bus receiver
CME3-2659 Send selected meter(s) to lock meters in wireless M-Bus receiver
CME3-2658 Clear all meters and associated keys in wireless M-Bus receiver
CME3-2657 Install all meters and keys in wireless M-Bus receiver


 

CMe3100 Firmware version 1.15.X
Firmware version 1.15.0

Release date: 2025-03-21

Important:

For BACnet plugin users. Before updating to firmware version 1.15.0 please ensure the following:

  • Make sure M-Bus Measurements Series exist for you BACnet objects: This is essential to keep your M-Bus to BACnet mappings and their associated object IDs during the upgrade process.

    Go to Measurement series and verify that all necessary series are available for your desired meters and sensors to ensure that the BACnet objects are properly migrated to the new firmware version.

  • Backup Recommendation: As an extra precaution, export your M-Bus to BACnet mappings as a .csv file before upgrading. This will allow you to import the mappings again if not successful with above bullet point.

Note! M-Bus to BACnet mappings moved from Dashboard > System panel > BACnet to Measurement series > BACnet map.

If you need further information before upgrading, please contact Elvaco Support.

Highlights:

  • Introduction of push reports via MQTT
  • New filtering functionality in the BACnet plugin

Table 196. Implemented changes

ID Description
CME3-2562 [ADD] More logging for SFTP handshake
CME3-2557 [ADD] Saving HTTP reports on local disk when transmission fails
CME3-2546 [ADD] Filtering functionality of M-Bus to BACnet mappings using measurement series, identical to Modbus plugin
CME3-2541 [FIX] Updated Measurement series template 'Elvaco Room Sensor' due to an issue with showing CO2 automatically.
CME3-2538 [ADD] MQTT support for push reports
CME3-2556 [FIX] Issue with Trust Store password when field left empty for HTTP Push reports


 

CMe3100 Firmware version 1.14.X

Elvaco strongly advice upgrading to the latest firmware on all units.

Firmware version 1.14.1

Release date: 2024-12-18

Important:

If you have problems in starting up the device with firmware 1.14.0, the solution is to insert the ethernet cable. This issue was introduced in 1.14.0.

Highlights:

  • Bug fixes

Table 197. Implemented changes

ID Description
CME3-2549 [FIX] Device ended up in a reboot loop when starting up without an ethernet cable
CME3-2543 [FIX] Translation issue in GUI ending up showing “Undefined”
CME3-2459 [FIX] Improved location of popup window appearing when deleting OBIS mappings in DLMS plugin


 

Firmware version 1.14.0

Release date: 2024-12-04

Important:

In previous firmwares, we identified a network related issue where the wrong broadcast address was set, when not on a /24 subnet, affecting BACnet users only.

Highlights:

  • Fixed issue for BACnet users where the broadcast address was wrongly set when using other than /24 network
  • Usability improvements for BACnet and Modbus
  • Security improvements

Table 198. Implemented changes

ID Description
CME3-2534 [FIX] Broadcast address was wrongly set when using other than /24 network
CME3-2328 [ADD] BACnet EDE-file export
CME3-2525 [ADD] Broadcast address is now visible in CMe3100 user interface > System > About page
CME3-2522 [ADD] Possibility to configure unicast I-Am responses in BACnet settings
CME3-2475 [FIX] Trying to set limits on BACnet objects types not supporting limits
CME3-2483 [FIX] Issue where editing in the Modbus map on pages other than the first would redirect users back to the first page
CME3-2510 [FIX] Modbus map editing dialog not visible
CME3-2498 [FIX] Improve input validation of all input fields
CME3-2486 [FIX] Improved security check of uploaded files in device
CME3-2482 [ADD] Updated the color design of the web interface
CME3-2444 [ADD] Improved design of firmware update page
CME3-2509 [FIX] Allowing the symbol '@' in the login username
CME3-2504 [FIX] If there is any error during startup of a service, the service will not be activated
CME3-2499 [FIX] Make internet status check more reliable
CME3-2517 [FIX] Error occurs when activating/deactivating translations in System > Translations


 

CMe3100 Firmware version 1.13.X

Elvaco strongly recommends upgrading to latest firmware on all units.

Firmware version 1.13.3

Release date: 2024-10-31

Important:

Firmware version 1.13.2 was wrongfully flagged by Sharepoint as malware.

Furthermore, we have identified a security risk in our CMe3100 that requires immediate attention. This release addresses this issue, and we recommend updating as soon as possible to ensure optimal security. Note that this issue does not affect devices restricted to private or closed networks.

We take the security of our products very seriously and are committed to providing you with a safe and reliable experience. We appreciate your understanding and thank you for your continued support as we enhance our product’s security.

For customers whose login usernames include any of the following special characters, these are not supported in firmware version 1.13.3. Please change your username before upgrading to avoid compatibility issues:

Unsupported characters: " & ' + & < = > @ `

Note: Support for the @ character will be reinstated in the next firmware release.

Highlights:

  • Security improvements of device.

Table 199. Implemented changes

ID Description
CME3-2487 [FIX] Updated Console (command line user interface) to deactivated as default on new devices and factory resetted devices
CME3-2488 [FIX] Fixed security risk for devices not on private or closed networks


 

Firmware version 1.13.2

Release date: 2024-10-24

Important:

All users are strongly recommended to upgrade to latest firmware version. Not just BACnet and Modbus users.

Highlights:

  • Patch release with smaller fixes, see below.

Table 200. Implemented changes

ID Description
CME3-2468 [FIX] The default value of Low limit of BACnet objects has now been updated to a large negative value instead of zero.
CME3-2467 [FIX] BACnet object status flags are new updated correctly
CME3-2464 [FIX] The Modbus constant field now has an improved check of the input value
CME3-2480 [Add] Added activate/deactivate all filtered mappings in Modbus plugin
CME3-2481 [Add] Re-implement scheduled reboots


 

Firmware version 1.13.0

Release date: 2024-10-15

Important:

All users are strongly recommended to upgrade to latest firmware. Not just BACnet and Modbus users.

Highlights:

  • Improved BACnet plugin in terms of usability and added new functionality
  • Improved usability of Modbus plugin
  • Enabled csv file export/import for setting up Modbus registers outside of CMe3100 web interface

Table 201. Implemented changes

ID Description
CME3-2293 [Added] Change BACnet object types from AnalogValue to AnalogInput
CME3-2443 [Added] More visible information in BACnet mappings table
CME3-2434 [Added] Possible to manually change names of BACnet objects via import file
CME3-2432 [Added] Multi-telegram support for BACnet
CME3-2452 [Added] Make BACnet device name and instance number configurable from client
CME3-2370 [Added] Feedback in UI when importing BACnet mappings
CME3-2438 [Added] Adjusted how BACnet instance number is derived from device serial number
CME3-2451 [Added] Implement BACnet NetworkPort object
CME3-2409 [Added] Simplify Modbus UI
CME3-2342 [Added] Import Modbus map using csv file
CME3-2433 [Fix] Sorting of Modbus map table
CME3-2381 [Added] Adjust how new measurementseries are allocated Modbus holding registers
CME3-2378 [Note] Format of the Modbus map export is updated in 1.13.0 and import feature requires the 1.13.0 format to work.
CME3-2455 [Added] Removed decimals numbers (“,000”) from Modbus values
CME3-2419 [Added] Increase support for mode 5 and mode 7 M-Bus telegram decryption
CME3-2456 [Fix] When a backup is done within 10 minutes of device startup it will be corrupt.
CME3-2418 [Fix] Verify NTP server reply to avoid misunderstanding timestamp
CME3-2408 [Fix] Swagger REST API via HTTPS
CME3-2353 [Fix] Telnet UI option always disabled


 

CMe3100 Firmware version 1.12.X

Elvaco recommends upgrading to latest firmware on all units.

Firmware version v1.12.1

Release date: 2024-06-28

Important:

In FTP Settings, to set the response time to unlimited in Firmware 1.11.0 and forward, the value needs to be set to 0.

In firmware v1.12.1, it does now migrate a set value of -1 to 0, to avoid issue for users that has this configuration in place.

Highlights:

  • See implemented changes.

Table 202. Implemented changes

ID Description
CME3-2392 Fixed issue with new FTP client (introduced in firmware v1.11.0) that does not support negative timeout values, while the old FTP client used -1 as unlimited timeout. The new client needs 0 instead, therefore migrating -1 to 0.


 

Firmware version v1.12.0

Release date: 2024-06-25

Important:

For users that have the BACnet plugin active! All object IDs will be changed due to new way of automatically generating and saving it into an internal database in the CMe3100. However, it is possible to change to current object IDs by using the new Import functionality, seen in the documentation.

Highlights:

  • Fixed issue with BACnet values not appearing in some receiving system.

Table 203. Implemented changes

ID Description
CME3-2334 [Fix] BACnet NaN for some values in some BACnet "readers"
CME3-2332 [Added] BACnet mappings table is sorted on BACnet object identification by default
CME3-2327 [Added] Object ID should be visible in mapping table in UI
CME3-2301 [Improvement] Improve loading indicator on BACnet mappings page
CME3-2255 [Update] Phone numbers in Report Templates needs to updated and/or removed
CME3-2321 [Added] Extend auto configuration so that encryption keys can be added
CME3-2136 [Added] Sync-Command added to auto configuration
CME3-2349 [Fix] Advanced settings on Services Push report fails for FTP timeout


 

CMe3100 Firmware version 1.11.X

Elvaco recommends upgrading to latest firmware on all units.

Firmware version v1.11.0

Release date: 2024-04-17

Important:

  • With this update, our product now sends reports to your FTP server using a temporary filename. Once the file has been successfully transmitted, it is renamed to a ".csv" extension. Therefore, please ensure that the FTP account used has permission to rename files.

Highlights:

  • Introduction of new BACnet license. There is a one time fee for acquiring it and firmware version 1.11.0 is needed to activate the license.

Table 204. Implemented changes

ID Description
CME3-2165 Added new feature enabling M-Bus to BACnet translation, which can be activated once purchasing a one fee license
CME3-1944 Added the Modbus constant in Modbus export and commissioning report
CME3-2251 Improved usability for FTP UI when configuring different protocols such as SFTP, FTPS, etc.
CME3-2262 Updated FTP reports are now first saved locally with a temporary name and only renamed to a ".csv" extension after a successful transfer to the FTP server, ensuring proper data handling and preventing premature processing.
CME3-2174 Improved usability for scaling in MODBUS map
CME3-2200 Fixed error message when setting duplicate MODBUS holding register
CME3-2287 Fixed issue during firmware file upload where new firmware version was listed as <unknown> instead of which FW version
CME3-2225 Fixed issue when uploading firmware file fails and duplicate file already exists
CME3-2219 Fixed SNMP checkbox in GUI to not always be unchecked
CME3-2230 Removed Excel as supported export format while CSV is still available
CME3-2131 Removed row number limitation in measurement series export
CME3-2182 Updated Java runtime to 11.70.16


 

CMe3100 Firmware version 1.10.X
Firmware version v1.10.1

Release date: 2023-12-06

Table 205. Implemented changes

ID Description
CME3-2188 Fixed scale constant for REST API endpoints


 

Firmware version v1.10.0

Release date: 2023-10-06

Notes:

  • All devices should be upgraded at nearest convenient point in time to let users benefit from improvements and stabilization of the device.
  • N.b! Old certificate of the computer setup program ‘Configure CMe3100’ has expired. New certificate for the setup file is implemented from this firmware (v1.10.0) and onwards.

    • Contact Elvaco support, if you are using a firmware older than 1.10.0 and need the setup file for installing or configuring your device via USB on your computer. However, if the configuration software is already installed, then there is not an issue.

Highlights:

  • Implemented measurement series template including CO2 for new products Elvaco Sense
  • Implemented the support of VIF/VIFE changes introduced in the M-Bus standard 13757-3:2018
  • Stability improvements
  • Fixed minor bug fixes and translation issues

Table 206. Implemented changes

ID Description
CME3-620 Implemented documentation for stream plugin in web interface
CME3-2132 Added CO2 measurement series for Elvaco Sense series
CME3-2010 Clicking edit/pen icon for measurement series should land on edit page
CME3-2114 Updated our M-Bus support to support VIF/VIFE changes introduced in 13757-3:2018
CME3-2124 Clicking edit/pen icon for meter should land on edit page
CME3-2134 Changed default trust store password
CME3-2142 Added license check as periodic check
CME3-762 Error labels in GUI wrong placement
CME3-788 Empty primary address on Add meter page results in error
CME3-790 Wait spinner not removed when input validation fails on "Add new meter" page
CME3-1850 Measurement series template for Elvaco wired room sensor stopped working
CME3-1985 JSON-RPC configuration page link results in a page saying "Unauthorized"
CME3-1990 Firmware update: Uploading the same file more than once results in a white screen
CME3-2003 REST API ignores the constant set in measurement series
CME3-2015 Modmap table search inconsistency
CME3-2019 CMe3100 CPUTemperatureProvider; Exception
CME3-2022 M-Bus interface to search validation of the address
CME3-2047 Password field is not masked on the login screen
CME3-2075 Include list command via telnet has no impact on the device
CME3-2108 Event id for log events are always -1 in log report
CME3-2115 The same M-Bus interface can be defined multiple times
CME3-2116 Renaming username does not check if the name already exists
CME3-2126 Delete function(s) translation page does not work
CME3-2128 Version missing on software update confirmation page
CME3-2151 REST documentation page (index_api.html) not rendered anymore
CME3-2153 Error editing type translation
CME3-2154 Incorrect script path to main.js in JSON-RPC pages
CME3-2155 Stream help page compiles at runtime (REMOVE)
CME3-2156 Load Stream Analyzer when the service is disabled results in Nullpointer Exception
CME3-2158 Automatic configuration update during startup not working
CME3-2173 Measurement series table exports are empty
CME3-2033 Investigate why the web server is not always responding to UndertowWatchdog
CME3-xxxx Other bug fixes and stability improvements


 

CMe3100 Firmware version 1.9.X

All devices should be upgraded at nearest convenient point in time to let users benefit from stabilization of the device.

Firmware version v1.9.11

Release date:2023-06-07

Table 207. Implemented changes

ID Description
CME3-2106 Fixed inconsistency between UI and configuration of device. Improved validation when restoring backup configuration.


 

Firmware version v1.9.10

Release date: 2023-05-16

Table 208. Implemented changes

ID Description
Implemented new rules of storing logfile
Fixed issue with device not preserving https service settings when upgrading from a FW version <1.9.0 to v1.9.9


 

Firmware version v1.9.9

Release date: 2023-03-17

Notes:

  • If using firmware version v1.9.0 or later and using custom trust store, verify in web interface that the following tick box is unticked:

    • Web interface –>services –> webserver –> Update trust store during next software update
  • If using CMe3100 and CMex50 with stream mode. Make sure to have CMeX50 firmware version v2.0.1 or newer, when updating CMe3100 to this firmware version.
  • New firmware uses by default the http chunked-transfer mode when sending reports.

    • When http chunked-mode is used, the Content-Length http header is not available

Table 209. Implemented changes

ID Description
CME3-190 Fixed that factory reset does not start when network cable is not connected
CME3-683 Show error value in measurement series template
CME3-845 Saving ftp reports locally should be improved
CME3-1836 Added REST: Historical measurement series data showing timezone
CME3-1853 CMe3100 logfile writes until unit is not reachable
CME3-1908 Clean mobiledata
CME3-1913 Added support for saving stream reports
CME3-1945 Fixed trust store update check box
CME3-1954 FTP reports: Error writing report .zip-file to disk.
CME3-1956 Remove feature to reboot on low memory (java)
CME3-1960 java.lang.StackOverflowError: regression introduced in MR-832
CME3-1722 resolv.conf being corrupt stops unit from starting
CME3-1726 New Zulu Java Available (11.60.20)
CME3-1727 Add email with TLS support
CME3-1869 Update Undertow webserver
CME3-648 Configure "error value" on multiple meters (measurement series)
CME3-1473 Shortened time taken to start a factory reset using physical button


 

Firmware version v1.9.8.1 - 1.9.8.3

Release date: 2023-01-11

Notes:

  • Stabilize and improve performance connected to memory utilization
  • Improved stream mode stability and performance
  • Fixed previous known issue with a capacity problem when using the following configuration simultaneously

    • Both virtual slave ports active
    • Continuous readout active
    • Firmware version older than 1.9

Firmware version v1.9.8.3

Table 210. Implemented changes

ID Description
Added measurement series for 'free' command
Limit heap size


 

Firmware version v1.9.8.2

Table 211. Implemented changes

ID Description
Uncaught exception in configuration upload
Stream: malformed cron patterns accepted
Stream: Avoid flooding log with stream log messages
Memory optimization
Stream: Reboot after resend fail
Stream: Make storing of analyzer data optional
Stream: Push Report resend support


 

Firmware version v1.9.8.1

Table 212. Implemented changes

ID Description
CME3-1909 Avoid flooding log with stream buffer full logs


 

Firmware version v1.9.8

Table 213. Implemented changes

ID Description
CME3-1870 Improve Stream service stability
CMe3-1866 Stream: improve export of in-memory database content
CMe3-1865 Correct free RAM calculation
CME3-1832 Fixed capacity problem having both virtual slave ports and continuous readout active simultaneously


 

Firmware version v1.9.6.1

Table 214. Implemented changes

ID Description
CME3-1822 Adjust XMX and XMS flags for java
CME3-1821 Update Undertow webserver
CME3-1749 Remove "ping home" function from UI to speed it up in closed networks
CME3-1747 Remove support for OpenVPN
CME3-1712 Web UI support for downloading heap dump
CME3-1711 Watchdog: Dump heap before low memory reboot
CME3-1709 Reboot on low memory
CME3-1706 Reboot now button on Restart web UI page
CME3-1704 Add JVM tools for heap memory management etc
CME3-1700 Web UI support for configuring scheduled reboot
CME3-1694 Add JVM free memory as measurement series source


 

Firmware version v1.9.5

Table 215. Implemented changes

ID Description
CME3-1685 Decoding error of GAV meter
CME3-1681 MAC address is shown on error pages when not logged in
CME3-1663 Watchdog might not work as planned
CME3-1661 Some help texts for default recipients have wrong placement
CME3-1638 Modbus float does not work
CME3-1632 The timestamp in the CMe3100 does not follow the standard
CME3-1617 "File per device" E-mail reports does not handle include list correctly
CME3-1592 Problem with stream and kamstrup meters
CME3-1590 Reports with one file/meter not working
CME3-1478 It is not possible to import metering series templates.
CME3-1459 Stream service configuration pages missing page footer
CME3-1457 REST service configuration pages missing page footer
CME3-1455 Modus service configuration pages missing page footer
CME3-1453 DLMS service configuration pages missing page footer
CME3-1451 JSON-RPC service configuration pages missing page footer
CME3-1015 Exporting measurement series template with special character makes export corrupt


 

Firmware version v1.9.4

Table 216. Implemented changes

ID Description
CME3-1574 Install progress information missing when searching for meters
CME3-1567 Password field is not masked in Default FTP settings
CME3-1519 Search for meters usability issues
CME3-1508 DNS can not be set
CME3-1503 Retrymax for pushreports does not work
CME3-1485 SFTP problem SETSTAT missmatch


 

Firmware version v1.9.3

Table 217. Implemented changes

ID Description
CME3-1510 169.254.254.2 is taken by CMe3100 software itself in some cases
CME3-1505 When performing configuration backup, current config might be corrupt


 

Firmware version v1.9.2

Table 218. Implemented changes

ID Description
CME3-1480 Make "Scheduled tasks" show ALL scheduled tasks
CME3-1417 Upgrade log4j to 2.16
CME3-1216 Log page is very slow to load
CME3-1185 Update i18n
CME3-1163 Add M-Bus master USB
CME3-1131 Redesign DLMS Channel Mapping page
CME3-785 Update CMe3100 pictures
CME3-714 Add REST documentation and helper UI
CME3-1497 CMe3100 was not using client cert authentication correct
CME3-1469 Random schedule might result in multiple jobs being triggered
CME3-1453 DLMS service configuration pages missing page footer
CME3-1431 Meassurement series value is corrupt using Modbus
CME3-1325 Autoconfig not working for stream device
CME3-1247 FTP error log contains obfuscated class information
CME3-1159 Green Led is indicating UI is accessable before webserver started
CME3-1149 When removing all Passive Meters and Linked Measurement series all Measurement series are removed
CME3-1132 When using REST interface OpenVPN doesn't disconnect correctly
CME3-942 Problem with passwords that contain "
CME3-793 Message in log (and event) when updating user record via REST is not always correct


 

Firmware version v1.9.1

Table 219. Implemented changes

ID Description
CME3-998 Remove unneeded dropdown at log page
CME3-991 Support async in CMe3100
CME3-941 Update AuthFilter to work in Undertow
CME3-898 HTTPS with undertow
CME3-895 REST should run with Undertow
CME3-866 Implement support for sending Push Reports via SFTP
CME3-850 Add support for creating configuration backup when performing software update
Decrypt OMS4 telegram
CME3-767 UI should compare that both separators don't match
CME3-742 Create reset password script
CME3-726 Add more information from watchdog to log
CME3-637 Add support for enabling/disabling plugin servlets at runtime
CME3-545 Include Elvaco-Plugin-Stream in main application
CME3-543 Include Elvaco-Plugin-Rest in main application
CME3-542 Include Elvaco-Plugin-Modbus in main application
CME3-541 Include Elvaco-Plugin-JSON-RPC in main application
CME3-540 Addons moved to services page
CME3-526 Update debug logo at log page
CME3-406 Allowlist should not be available on DLMS Push Reports page
CME3-838


 

Firmware version v1.9.0

Table 220. Implemented changes

ID Description
CME3-208 CMe3100 Push Reports should handle TLS 1.2
CME3-526 Addons moved to services page
CME3-621 Update the graphical profile
CME3-637 Add more information from watchdog to log
CME3-720 Add support for changing report separator from ";" to another separator
CME3-764 CMe3100 should be able to decrypt OMS 4.02 (Level 7)
CME3-850 Support for creating configuration backup during software update
CME3-856 Support for sending reports via SFTP
CME3-998 Remove unneeded drop down at log page
CME3-587 Basic auth is not working with default HTTP settings
CME3-589 Deprecated Modbus holding registers cannot be removed
CME3-667 Modbus mapping export data is truncated
CME3-706 Device type ids > 64 results in meters being inaccessible in UI
CME3-735 Exception when adding meter interface to search
CME3-746 Certificate for Windows installer has expired
CME3-383 ‘Allow list’ should not be available on DLMS Push Reports page
CME3-934 Scheduled report setting not changed after config sync
CME3-944 Factory reset via telnet has no effect
CME3-979 Deprecated endpoint /device/values/{identification}
CME3-999 Factory reset does not do full factory reset
CME3-1001 Measurement series templates gets corrupted when imported
CME3-1003 Stream mode missing meters
CME3-1019 Updating status log is not working when 'Continues Readout' is activated


 

CMe3100 Firmware version 1.8.X
Firmware version v1.8.19

Table 221. Implemented changes

ID Description
CME3-708 Continuous readout only updates with 1 min interval
CME3-740 Time input to backup settings script is not updated


 

Firmware version v1.8.18

Table 222. Implemented changes

ID Description
CME3-661 Save FTP Push Reports on device and download them from UI
CME3-193 When not logged in, MAC address is shown in header
CME3-658 Endless storevalue
CME3-682 White page in UI after failing to upload measurement template
CME3-697 Backup settings not fully translated to German


 

Firmware version v1.8.17

Table 223. Implemented changes

ID Description
CME3-638 JVM crash triggered during application launch


 

Firmware version v1.8.16

Table 224. Implemented changes

ID Description
CME3-617 Change language strings in language selector (English, Deutsch, Svenska)
CME3-623 Errors in auto configuration files are hard to identify (improve logging)
CME3-624 JSON-RPC plugin operations returns no data


 

Firmware version v1.8.15

Table 225. Implemented changes

ID Description
CME3-595 Added export functionality at analyses section in Stream mode
CME3-612 Web user interface translated to German
CME3-590 DLMS mapping list is not working with warmwater
CME3-591 DLMS should not create device map records if man/devtype/version is not valid
CME3-592 DLMS should not create session if there is no data to send
CME3-601 FTPS gives error message "Protection buffer size not negotiated"
CME3-611 Support MCal missing (VIF extended code table)


 

Firmware version v1.8.14

Table 226. Implemented changes

ID Description
CME3-477 M-Bus parser does not support US gallons in mbus.dib-field
CME3-534 Stream mode should handle encrypted devices
CME3-560 Continuously sending NKE
CME3-564 Poor documentation of JSON plugin
CME3-573 Add logo for Integra Metering


 

Firmware version v1.8.13

Table 227. Implemented changes

ID Description
CME3-439 Stream mode usability improvements
CME3-442
CME3-462
CME3-478 Platform upgrade
CME3-448
CME3-500
CME3-443 Deactivate measurement series when license larger than 256
CME3-481 Improve device logging options
CME3-502 Add information text for readout vs number of meters
CME3-510 Redesign language selector in UI
CME3-425 Spelling error in measurement series template (secundary -> secondary)
CME3-504 Device Logical name in UI is not correct


 

Firmware version v1.8.12

Table 228. Implemented changes

ID Description
CME3-397 Add temperature information in maintenance log
CME3-419 Add CMe3100 temperature as measurement series source
CME3-136 Missing timeframe for expiry time at measurement series
CME3-278 FTP timeout field is missing in the web interface
CME3-369 M-Bus parser error
CME3-441 Stream mode floods log


 

Firmware version v1.8.11

Table 229. Implemented changes

ID Description
CME3-411 Sending nke=253 when experiencing M-Bus decoding errors


 

Firmware version v1.8.10

Table 230. Implemented changes

ID Description
CME3-133 New logotypes for meter manufacturers added
CME3-387 CMe3100 is now able to handle intermittent error in Badger Water Meter E-Series not getting selected/deselected during search/readout. Feature may be enabled/disabled using configuration. See new configuration parameters device.mbus.nke.*.
CME3-396 A new connection is now established for each new DLMS Push Report
CME3-235 Help text of default e-mail sender address is not correct
CME3-353 FTP timeout field is missing in the web interface
CME3-356 Setting a recurrent reboot via cron does not work
CME3-389 REST call may result in the memory getting full


 

Firmware version v1.8.9

Table 231. Implemented changes

ID Description
CME3-335 Cron is not updated when syncing settings (auto configuration)
CME3-337 Swedish translation on the web server configuration page (Configuration/Services/Webserver) is wrong


 

Firmware version v1.8.8

Table 232. Implemented changes

ID Description
CME3-334 DLMS did not handle increasing frame counters correctly when DLMS clients performed pull requests.


 

Firmware version v1.8.7

Table 233. Implemented changes

ID Description
CME3-294 Fraud log events in DLMS plugin are now divided. One report for gateway events and one report per meter for meter events. In previous versions they were all sent in one report.
CME3-314 Column ‘logid’ for log event added when exporting logs.
CME3-315 Column ‘created’ extended to show also milliseconds of the log event when exporting logs.


 

Firmware version v1.8.6

Table 234. Implemented changes

ID Description
CME3-237 DLMS plugin user interface improvements: OBIS codes are now configurable
CME3-268 Added two new type of Report Templates (e-mail, FTP and HTTP)


 

Firmware version v1.8.5

Table 235. Implemented changes

ID Description
CME3-234 Added possibility to set runbefore commands in web interface
CME3-160 Advanced meter search made more user-friendly
CME3-231 Some types of meters are not reacting to storevalue commands from CMe3100
CME3-230 Some types of meters cannot be installed by CMe3100
CME3-198 When auto configuration has been started, it cannot be disabled
CME3-138 Temporary folders are not deleted at reboots


 

Firmware version v1.8.4

Table 236. Implemented changes

ID Description
CME3-205 Meter installation is interrupted due to collisions on the M-Bus line


 

Firmware version v1.8.3

Table 237. Implemented changes

ID Description
CME3-210 In cases when CMe3100 does not receive a 2xx response from the HTTP server, Push Reports will not be sent
CME3-163 An error in the product third-party library prevents secure DLMS Push Reports from being sent
CME3-162 The DLMS plugin does not handle some integers correctly


 

Firmware version v1.8.2

Table 238. Implemented changes

ID Description
CME3-111 Users are now able to export raw M-Bus data via the REST interface
CME3-125 “REST: UserLink – Delete userlink (s)” returns failure message when the operation is successful
CME3-124 Some REST features generate incorrect response messages
CME3-113 DLMS: Secured push is not according to standard
CME3-112 Unable to add or edit content in the user.cfg configuration file via REST
CME3-102 Device fails to upload data via FTPS in some cases
CME3-26 Device accepts uploads of software file formats that it is unable to handle


 

Firmware version v1.8.1

Table 239. Implemented changes

ID Description
CME3-79 Existing meter icons have been improved
CME3-61 Change log has been replaced by a link to the corresponding information on the website
CME3-14 Missing meter icons have been implemented in the CMe3100 web interface
CME3-92 The time of the device cannot be set manually
CME3-91 An old user’s manual reference has not been removed from the web interface
CME3-90 The online resources section links to the old website
CME3-87 Certain URIs are not handled properly
CME3-12 M-Bus telegram is not published in system log when an M-Bus decode exception is caught
CME3-11 Duplicated devices in meter list are ignored


 

Firmware version v1.8.0

Table 240. Implemented changes

ID Description
4574 Device now handles all HTTP response codes in the 2xx range
3954 Device now supports FTPS Push Reports


 

CMe3100 Firmware version 1.7.X
Firmware version v1.7.4

Table 241. Implemented changes

ID Description
4514 REST: Delete log is removed to improve security, now also removed from help section
4491 Default time synchronization is changed to 11:30 pm/am instead of 0:30 pm/am
4055 REST: Device can now be updated via identification field (/device/update/identification/{identification}/…)
4230 Meters with compact frame cannot be decrypted (e.g. Kamstrup MC21)


 

Firmware version v1.7.3

Table 242. Implemented changes

ID Description
4044 Measurement series template for gas meters added
3902 License information available in status command
3739 It is now possible to execute auto configuration automatically after it has been saved
4230 Report schedule selection is empty after update
4063 Meter data is read correctly via virtual slave port in continues mode
3655 The option to delete records from the system log via REST interface is removed to improve security


 

Firmware version v1.7.2

Table 243. Implemented changes

ID Description
4178 Virtual M-Bus communication starts with wrong configuration upon reboot


 

Firmware version v1.7.1

Table 244. Implemented changes

ID Description
4043 DLMS does not handle interpunctuation characters as part of octet strings


 

Firmware version v1.7.0

Table 245. Implemented changes

ID Description
3547 New DLMS event "User trying to lower security policy" is added to system lo
3557 Device monitoring is now available using SNMP
3936 Raw and decoded M-Bus data are now available in DLMS
3950 System log event ID is now included in log Push Reports
3960 Certificate handling for HTTPS is improved to allow more advanced setups
4023 Boot counter is now added to device statistics (Device > About)
3686 Format specifiers are sometimes not resolved in system log entry texts
3843 Push Report number is wrong in system log entry text for configuration change events


 

CMe3100 Firmware version 1.6.X
Firmware version v1.6.3

Table 246. Implemented changes

ID Description
3981 Software package update to support improved production process


 

Firmware version v1.6.2

Table 247. Implemented changes

ID Description
2537 HTTP Push Report is logged as failed if receiving web server does not respond with a body
3844 Save & Send test report does not work if security level 1 password is set
3849 Unable to use individual settings for Authentication mode in HTTP Push Reports, default settings are always used


 

Firmware version v1.6.1

Table 248. Implemented changes

ID Description
3499 Mass deployment of firmware updates, configurations and licenses is now possible using the EDM tool
3539 Measurement serie templates can now be imported and exported to simplify configuration
3566 REST interface is now supporting Continuous read out mode using mdmdata/api/single/ or mdmdata/api/multi/
3570 Modbus slave address can now be changed (Modbus add-on)
3657 Limit for exporting measurement series is now increased to 5000
3658 "Signal Strength" is now added to measurement series template "Electricity, ABB, general"
3410 Push Reports does not work if schedule is set to daily reports
3467 Meter readout cycle is aborted if a wireless meter is faulty
3560 Heavy load on Virtual M-Bus over TCP/IP sometimes causes "Error connecting."
3561 Scheduling a Push Report with a shorter interval than it takes to complete the report sending causes the device to become overloaded and reboot.
3564 Display error value in settings for Measurement series does not work
3567 Unable to detect a lost Ethernet connection
3669 Sending value or log Push Report causes report service to hang if reports are larger than 100 values per meter / entries (v1.6.0)
3700 Factory reset change the hostname to CMe3100-0016000000
3703 The M-Bus interface sometimes hangs if multiple services access the M-Bus
3727 DLMS connection idle timeout setting does not work
3766 "filter.device.includelist" setting does not work with Report Templates containing multiple meters in a single file


 

Firmware version v1.6.0

Table 249. Implemented changes

ID Description
3293 Database performance is improved
3433 Automatic retransmit of Push Reports that has failed to reach its destination is now improved
3435 System log is reworked with a complete new set of entries
3466 Option to recover password via e-mail on My Account page is removed to improve security
3474 New feature "DLMS Plugin" is added to list of available add-ons
3488 Link-local address for USB network interface is changed from 192.168.100.1 to 169.254.254.1 to avoid conflicting IP addresses
3490 New feature "Continuous readout mode"
3497 Integration with Kabona systems are now streamlined
3206 Push Report schedule automatically aligns with meter readout schedule
3175 Requesting data through Virtual M-Bus using secondary address sometimes returns wrong/no data
3195 Changing port for the Web server service does not display the "reboot is required" banner
3276 Validation of email address does not allow two dots, e.g. username@mail.co.uk
3340 Push Reports does not handle huge meter values (greater than unsigned int 32)
3346 Unable to decrypt telegrams from CMeX20W, results in error "unknown encryption method"
3349 Add-on settings are not stored when creating a backup file
3369 Meter readout does not show error message when unable to connect to the meter (applies to all versions 1.4.x)
3482 Reports can be malformed if M-Bus field of type string contains non-ascii characters
3489 Unable to search log entries if the search string contains an apostrophe sign (')


 

CMe3100 Firmware version 1.4.X
Firmware version v1.4.4

Table 250. Implemented changes

ID Description
3427 Size of system log increased, and disk cleanup procedure improved
3428 HTTP Push Reports now supports HTTPS
3426 System log is deleted when maximum database size is reached
3436 Columns between "MOID" and "Secondary address" is in wrong order for report template 1112, 2112, 3112 (v1.4.3)


 

Firmware version v1.4.3

Table 251. Implemented changes

ID Description
3350 System security is improved
3365 Client certificates can now be used to authenticate clients connecting to the web server or REST interface (Services - Web server)HTTPS
3265 Unable to download backup file from file repository if larger than 40MB
3400 Manufacturer name is incorrectly shown when importing encryption keys with manufacturer information
3402 An extra tab can be present in the commissioning report


 

Firmware version v1.4.2

Table 252. Implemented changes

ID Description
3353 Upgrading to v1.4.1 when ModBus plugin is installed sometimes causes the ModBus mapping to disappear


 

Firmware version v1.4.1

Table 253. Implemented changes

ID Description
3292 The factory reset function causes database settings to become incorrect. Ref: PQN 22502-5
3297 The option to delete records from the system log is removed to improve security
3303 Export function in System log can now export the full log as csv (previously limited to 1000 entries)


 

Firmware version v1.4.0

Table 254. Implemented changes

ID Description
3079 Change device is removed to adapt to a coming feature update
2719 Virtual M-Bus can now support enhanced secondary addressing (provided for compatibility reasons)
3243 JavaScript feature in Measurement series is temporarily disabled until a moreuser friendly API has been developed
3221 Measure object ID is added as a separate column to export files from Modbus mappings and file is now filtered according to filter settings on page
3243 JavaScript feature in Measurement series is temporarily disabled until a moreuser friendly API has been developed
3221 Measure object ID is added as a separate column to export files from Modbus mappings and file is now filtered according to filter settings on page
3170 Timeout settings for ftp, http, and email, are added to settings for Services > Push Reports (default is now 60 sec)
3088 Date and time for when device was started is added to the System Panel
3084 Push Report URL is now allowing all types of characters to enable e.g. request parameters
2917 Modbus constant in Measurement series > Modbus Map can now handle decimal constants
2392 Presets for week, month and quarter are added to Report schedule control
3117 New feature "Adaptive Retries" is added to the Push Reports service
3081 Sending Push Reports can hang the report service if receiving HTTP server can't be reached
2716 Sending E-Mail and FTP Push Reports can hang the report service if the receiving server does not manage the connection correctly
3261 Device backup does not store all configuration settings in backup (only meter value database)
3080 System log is flooded with "Connection refused" when using HTTPS to connect to the web interface
2538 Report columns and data is sometimes mismatched if meters are using multi telegram
3254 Device does not warn user if there is not enough disk space to perform a backup which can cause the device to become unresponsive (will need factory reset)
3253 Date & time icon in installation panel is showing a warning when accepted time difference is set to 0 even if time sync is working correctly
3236 Support links are in Swedish when selected language is English
3201 Unable to set Manual DNS if Dynamic IP is chosen
3193 Firmware update dialog is displayed incorrectly in IE 11
3175 Requesting data through Virtual M-Bus using secondary address sometimes returns wrong data
3132 Virtual M-Bus does not respond with ACK when receiving SND_NKE and using secondary addressing
3082 Unable to set time using Console interface
3072 Editing settings for a faulty meter causes an error page to be displayed
3071 Export file from measurement series table is incorrect
3007 REST interface example about report settings does not work
3002 REST interface GET /system/time sometimes return wrong moth
2918 Changing host name (Network settings) sometimes fails and causes and host name to be reverted to default name
2749 REST interface device command does not work
2557 Sorting meter list on status column sometimes does not work
2438 Changing from static to dynamic IP causes an error if the device has not a working network connection


 