Release notes
For: CMe3100
Elvaco recommends upgrading to latest firmware on all units.
Release date: 2024-06-28
Important:
In FTP Settings, to set the response time to unlimited in Firmware 1.11.0 and forward, the value needs to be set to 0.
In firmware v1.12.1, it does now migrate a set value of -1 to 0, to avoid issue for users that has this configuration in place.
Highlights:
-
See implemented changes.
Table 129. Implemented changes
ID |
Description |
---|---|
CME3-2392 |
Fixed issue with new FTP client (introduced in firmware v1.11.0) that does not support negative timeout values, while the old FTP client used -1 as unlimited timeout. The new client needs 0 instead, therefore migrating -1 to 0. |
Release date: 2024-06-25
Important:
For users that have the BACnet plugin active! All object IDs will be changed due to new way of automatically generating and saving it into an internal database in the CMe3100. However, it is possible to change to current object IDs by using the new Import functionality, seen in the documentation.
Highlights:
-
Fixed issue with BACnet values not appearing in some receiving system.
Table 130. Implemented changes
ID |
Description |
---|---|
CME3-2334 |
[Fix] BACnet NaN for some values in some BACnet "readers" |
CME3-2332 |
[Added] BACnet mappings table is sorted on BACnet object identification by default |
CME3-2327 |
[Added] Object ID should be visible in mapping table in UI |
CME3-2301 |
[Improvement] Improve loading indicator on BACnet mappings page |
CME3-2255 |
[Update] Phone numbers in Report Templates needs to updated and/or removed |
CME3-2321 |
[Added] Extend auto configuration so that encryption keys can be added |
CME3-2136 |
[Added] Sync-Command added to auto configuration |
CME3-2349 |
[Fix] Advanced settings on Services Push report fails for FTP timeout |
Elvaco recommends upgrading to latest firmware on all units.
Release date: 2024-04-17
Highlights:
-
Introduction of new BACnet license. There is a one time fee for acquiring it and firmware version 1.11.0 is needed to activate the license.
Table 131. Implemented changes
ID |
Description |
---|---|
CME3-2165 |
Added new feature enabling M-Bus to BACnet translation, which can be activated once purchasing a one fee license |
CME3-1944 |
Added the Modbus constant in Modbus export and commissioning report |
CME3-2251 |
Improved usability for FTP UI when configuring different protocols such as SFTP, FTPS, etc. |
CME3-2174 |
Improved usability for scaling in MODBUS map |
CME3-2200 |
Fixed error message when setting duplicate MODBUS holding register |
CME3-2287 |
Fixed issue during firmware file upload where new firmware version was listed as <unknown> instead of which FW version |
CME3-2225 |
Fixed issue when uploading firmware file fails and duplicate file already exists |
CME3-2219 |
Fixed SNMP checkbox in GUI to not always be unchecked |
CME3-2230 |
Removed Excel as supported export format while CSV is still available |
CME3-2131 |
Removed row number limitation in measurement series export |
CME3-2182 |
Updated Java runtime to 11.70.16 |
Release date: 2023-12-06
Release date: 2023-10-06
Notes:
-
All devices should be upgraded at nearest convenient point in time to let users benefit from improvements and stabilization of the device.
-
N.b! Old certificate of the computer setup program ‘Configure CMe3100’ has expired. New certificate for the setup file is implemented from this firmware (v1.10.0) and onwards.
-
Contact Elvaco support, if you are using a firmware older than 1.10.0 and need the setup file for installing or configuring your device via USB on your computer. However, if the configuration software is already installed, then there is not an issue.
-
Highlights:
-
Implemented measurement series template including CO2 for new products Elvaco Sense
-
Implemented the support of VIF/VIFE changes introduced in the M-Bus standard 13757-3:2018
-
Stability improvements
-
Fixed minor bug fixes and translation issues
Table 133. Implemented changes
ID |
Description |
---|---|
CME3-620 |
Implemented documentation for stream plugin in web interface |
CME3-2132 |
Added CO2 measurement series for Elvaco Sense series |
CME3-2010 |
Clicking edit/pen icon for measurement series should land on edit page |
CME3-2114 |
Updated our M-Bus support to support VIF/VIFE changes introduced in 13757-3:2018 |
CME3-2124 |
Clicking edit/pen icon for meter should land on edit page |
CME3-2134 |
Changed default trust store password |
CME3-2142 |
Added license check as periodic check |
CME3-762 |
Error labels in GUI wrong placement |
CME3-788 |
Empty primary address on Add meter page results in error |
CME3-790 |
Wait spinner not removed when input validation fails on "Add new meter" page |
CME3-1850 |
Measurement series template for Elvaco wired room sensor stopped working |
CME3-1985 |
JSON-RPC configuration page link results in a page saying "Unauthorized" |
CME3-1990 |
Firmware update: Uploading the same file more than once results in a white screen |
CME3-2003 |
REST API ignores the constant set in measurement series |
CME3-2015 |
Modmap table search inconsistency |
CME3-2019 |
CMe3100 CPUTemperatureProvider; Exception |
CME3-2022 |
M-Bus interface to search validation of the address |
CME3-2047 |
Password field is not masked on the login screen |
CME3-2075 |
Include list command via telnet has no impact on the device |
CME3-2108 |
Event id for log events are always -1 in log report |
CME3-2115 |
The same M-Bus interface can be defined multiple times |
CME3-2116 |
Renaming username does not check if the name already exists |
CME3-2126 |
Delete function(s) translation page does not work |
CME3-2128 |
Version missing on software update confirmation page |
CME3-2151 |
REST documentation page (index_api.html) not rendered anymore |
CME3-2153 |
Error editing type translation |
CME3-2154 |
Incorrect script path to main.js in JSON-RPC pages |
CME3-2155 |
Stream help page compiles at runtime (REMOVE) |
CME3-2156 |
Load Stream Analyzer when the service is disabled results in Nullpointer Exception |
CME3-2158 |
Automatic configuration update during startup not working |
CME3-2173 |
Measurement series table exports are empty |
CME3-2033 |
Investigate why the web server is not always responding to UndertowWatchdog |
CME3-xxxx |
Other bug fixes and stability improvements |
All devices should be upgraded at nearest convenient point in time to let users benefit from stabilization of the device.
Release date:2023-06-07
Table 134. Implemented changes
ID |
Description |
---|---|
CME3-2106 |
Fixed inconsistency between UI and configuration of device. Improved validation when restoring backup configuration. |
Release date: 2023-05-16
Table 135. Implemented changes
ID |
Description |
---|---|
Implemented new rules of storing logfile |
|
Fixed issue with device not preserving https service settings when upgrading from a FW version <1.9.0 to v1.9.9 |
Release date: 2023-03-17
Notes:
-
If using firmware version v1.9.0 or later and using custom trust store, verify in web interface that the following tick box is unticked:
-
Web interface –>services –> webserver –> Update trust store during next software update
-
-
If using CMe3100 and CMex50 with stream mode. Make sure to have CMeX50 firmware version v2.0.1 or newer, when updating CMe3100 to this firmware version.
-
New firmware uses by default the http chunked-transfer mode when sending reports.
-
When http chunked-mode is used, the Content-Length http header is not available
-
Table 136. Implemented changes
ID |
Description |
---|---|
CME3-190 |
Fixed that factory reset does not start when network cable is not connected |
CME3-683 |
Show error value in measurement series template |
CME3-845 |
Saving ftp reports locally should be improved |
CME3-1836 |
Added REST: Historical measurement series data showing timezone |
CME3-1853 |
CMe3100 logfile writes until unit is not reachable |
CME3-1908 |
Clean mobiledata |
CME3-1913 |
Added support for saving stream reports |
CME3-1945 |
Fixed trust store update check box |
CME3-1954 |
FTP reports: Error writing report .zip-file to disk. |
CME3-1956 |
Remove feature to reboot on low memory (java) |
CME3-1960 |
java.lang.StackOverflowError: regression introduced in MR-832 |
CME3-1722 |
resolv.conf being corrupt stops unit from starting |
CME3-1726 |
New Zulu Java Available (11.60.20) |
CME3-1727 |
Add email with TLS support |
CME3-1869 |
Update Undertow webserver |
CME3-648 |
Configure "error value" on multiple meters (measurement series) |
CME3-1473 |
Shortened time taken to start a factory reset using physical button |
Release date: 2023-01-11
Notes:
-
Stabilize and improve performance connected to memory utilization
-
Improved stream mode stability and performance
-
Fixed previous known issue with a capacity problem when using the following configuration simultaneously
-
Both virtual slave ports active
-
Continuous readout active
-
Firmware version older than 1.9
-
Firmware version v1.9.8.3
Table 137. Implemented changes
ID |
Description |
---|---|
Added measurement series for 'free' command |
|
Limit heap size |
Firmware version v1.9.8.2
Table 138. Implemented changes
ID |
Description |
---|---|
Uncaught exception in configuration upload |
|
Stream: malformed cron patterns accepted |
|
Stream: Avoid flooding log with stream log messages |
|
Memory optimization |
|
Stream: Reboot after resend fail |
|
Stream: Make storing of analyzer data optional |
|
Stream: Push Report resend support |
Firmware version v1.9.8.1
Table 139. Implemented changes
ID |
Description |
---|---|
CME3-1909 |
Avoid flooding log with stream buffer full logs |
Table 140. Implemented changes
ID |
Description |
---|---|
CME3-1870 |
Improve Stream service stability |
CMe3-1866 |
Stream: improve export of in-memory database content |
CMe3-1865 |
Correct free RAM calculation |
CME3-1832 |
Fixed capacity problem having both virtual slave ports and continuous readout active simultaneously |
Table 141. Implemented changes
ID |
Description |
---|---|
CME3-1822 |
Adjust XMX and XMS flags for java |
CME3-1821 |
Update Undertow webserver |
CME3-1749 |
Remove "ping home" function from UI to speed it up in closed networks |
CME3-1747 |
Remove support for OpenVPN |
CME3-1712 |
Web UI support for downloading heap dump |
CME3-1711 |
Watchdog: Dump heap before low memory reboot |
CME3-1709 |
Reboot on low memory |
CME3-1706 |
Reboot now button on Restart web UI page |
CME3-1704 |
Add JVM tools for heap memory management etc |
CME3-1700 |
Web UI support for configuring scheduled reboot |
CME3-1694 |
Add JVM free memory as measurement series source |
Table 142. Implemented changes
ID |
Description |
---|---|
CME3-1685 |
Decoding error of GAV meter |
CME3-1681 |
MAC address is shown on error pages when not logged in |
CME3-1663 |
Watchdog might not work as planned |
CME3-1661 |
Some help texts for default recipients have wrong placement |
CME3-1638 |
Modbus float does not work |
CME3-1632 |
The timestamp in the CMe3100 does not follow the standard |
CME3-1617 |
"File per device" E-mail reports does not handle include list correctly |
CME3-1592 |
Problem with stream and kamstrup meters |
CME3-1590 |
Reports with one file/meter not working |
CME3-1478 |
It is not possible to import metering series templates. |
CME3-1459 |
Stream service configuration pages missing page footer |
CME3-1457 |
REST service configuration pages missing page footer |
CME3-1455 |
Modus service configuration pages missing page footer |
CME3-1453 |
DLMS service configuration pages missing page footer |
CME3-1451 |
JSON-RPC service configuration pages missing page footer |
CME3-1015 |
Exporting measurement series template with special character makes export corrupt |
Table 143. Implemented changes
ID |
Description |
---|---|
CME3-1574 |
Install progress information missing when searching for meters |
CME3-1567 |
Password field is not masked in Default FTP settings |
CME3-1519 |
Search for meters usability issues |
CME3-1508 |
DNS can not be set |
CME3-1503 |
Retrymax for pushreports does not work |
CME3-1485 |
SFTP problem SETSTAT missmatch |
Table 144. Implemented changes
ID |
Description |
---|---|
CME3-1510 |
169.254.254.2 is taken by CMe3100 software itself in some cases |
CME3-1505 |
When performing configuration backup, current config might be corrupt |
Table 145. Implemented changes
ID |
Description |
---|---|
CME3-1480 |
Make "Scheduled tasks" show ALL scheduled tasks |
CME3-1417 |
Upgrade log4j to 2.16 |
CME3-1216 |
Log page is very slow to load |
CME3-1185 |
Update i18n |
CME3-1163 |
Add M-Bus master USB |
CME3-1131 |
Redesign DLMS Channel Mapping page |
CME3-785 |
Update CMe3100 pictures |
CME3-714 |
Add REST documentation and helper UI |
CME3-1497 |
CMe3100 was not using client cert authentication correct |
CME3-1469 |
Random schedule might result in multiple jobs being triggered |
CME3-1453 |
DLMS service configuration pages missing page footer |
CME3-1431 |
Meassurement series value is corrupt using Modbus |
CME3-1325 |
Autoconfig not working for stream device |
CME3-1247 |
FTP error log contains obfuscated class information |
CME3-1159 |
Green Led is indicating UI is accessable before webserver started |
CME3-1149 |
When removing all Passive Meters and Linked Measurement series all Measurement series are removed |
CME3-1132 |
When using REST interface OpenVPN doesn't disconnect correctly |
CME3-942 |
Problem with passwords that contain " |
CME3-793 |
Message in log (and event) when updating user record via REST is not always correct |
Table 146. Implemented changes
ID |
Description |
---|---|
CME3-998 |
Remove unneeded dropdown at log page |
CME3-991 |
Support async in CMe3100 |
CME3-941 |
Update AuthFilter to work in Undertow |
CME3-898 |
HTTPS with undertow |
CME3-895 |
REST should run with Undertow |
CME3-866 |
Implement support for sending Push Reports via SFTP |
CME3-850 |
Add support for creating configuration backup when performing software update |
Decrypt OMS4 telegram |
|
CME3-767 |
UI should compare that both separators don't match |
CME3-742 |
Create reset password script |
CME3-726 |
Add more information from watchdog to log |
CME3-637 |
Add support for enabling/disabling plugin servlets at runtime |
CME3-545 |
Include Elvaco-Plugin-Stream in main application |
CME3-543 |
Include Elvaco-Plugin-Rest in main application |
CME3-542 |
Include Elvaco-Plugin-Modbus in main application |
CME3-541 |
Include Elvaco-Plugin-JSON-RPC in main application |
CME3-540 |
Addons moved to services page |
CME3-526 |
Update debug logo at log page |
CME3-406 |
Allowlist should not be available on DLMS Push Reports page |
CME3-838 |
Table 147. Implemented changes
ID |
Description |
---|---|
CME3-208 |
CMe3100 Push Reports should handle TLS 1.2 |
CME3-526 |
Addons moved to services page |
CME3-621 |
Update the graphical profile |
CME3-637 |
Add more information from watchdog to log |
CME3-720 |
Add support for changing report separator from ";" to another separator |
CME3-764 |
CMe3100 should be able to decrypt OMS 4.02 (Level 7) |
CME3-850 |
Support for creating configuration backup during software update |
CME3-856 |
Support for sending reports via SFTP |
CME3-998 |
Remove unneeded drop down at log page |
CME3-587 |
Basic auth is not working with default HTTP settings |
CME3-589 |
Deprecated Modbus holding registers cannot be removed |
CME3-667 |
Modbus mapping export data is truncated |
CME3-706 |
Device type ids > 64 results in meters being inaccessible in UI |
CME3-735 |
Exception when adding meter interface to search |
CME3-746 |
Certificate for Windows installer has expired |
CME3-383 |
‘Allow list’ should not be available on DLMS Push Reports page |
CME3-934 |
Scheduled report setting not changed after config sync |
CME3-944 |
Factory reset via telnet has no effect |
CME3-979 |
Deprecated endpoint /device/values/{identification} |
CME3-999 |
Factory reset does not do full factory reset |
CME3-1001 |
Measurement series templates gets corrupted when imported |
CME3-1003 |
Stream mode missing meters |
CME3-1019 |
Updating status log is not working when 'Continues Readout' is activated |
Table 148. Implemented changes
ID |
Description |
---|---|
CME3-708 |
Continuous readout only updates with 1 min interval |
CME3-740 |
Time input to backup settings script is not updated |
Table 149. Implemented changes
ID |
Description |
---|---|
CME3-661 |
Save FTP Push Reports on device and download them from UI |
CME3-193 |
When not logged in, MAC address is shown in header |
CME3-658 |
Endless storevalue |
CME3-682 |
White page in UI after failing to upload measurement template |
CME3-697 |
Backup settings not fully translated to German |
Table 150. Implemented changes
ID |
Description |
---|---|
CME3-638 |
JVM crash triggered during application launch |
Table 151. Implemented changes
ID |
Description |
---|---|
CME3-617 |
Change language strings in language selector (English, Deutsch, Svenska) |
CME3-623 |
Errors in auto configuration files are hard to identify (improve logging) |
CME3-624 |
JSON-RPC plugin operations returns no data |
Table 152. Implemented changes
ID |
Description |
---|---|
CME3-595 |
Added export functionality at analyses section in Stream mode |
CME3-612 |
Web user interface translated to German |
CME3-590 |
DLMS mapping list is not working with warmwater |
CME3-591 |
DLMS should not create device map records if man/devtype/version is not valid |
CME3-592 |
DLMS should not create session if there is no data to send |
CME3-601 |
FTPS gives error message "Protection buffer size not negotiated" |
CME3-611 |
Support MCal missing (VIF extended code table) |
Table 153. Implemented changes
ID |
Description |
---|---|
CME3-477 |
M-Bus parser does not support US gallons in mbus.dib-field |
CME3-534 |
Stream mode should handle encrypted devices |
CME3-560 |
Continuously sending NKE |
CME3-564 |
Poor documentation of JSON plugin |
CME3-573 |
Add logo for Integra Metering |
Table 154. Implemented changes
ID |
Description |
---|---|
CME3-439 |
Stream mode usability improvements |
CME3-442 |
|
CME3-462 |
|
CME3-478 |
Platform upgrade |
CME3-448 |
|
CME3-500 |
|
CME3-443 |
Deactivate measurement series when license larger than 256 |
CME3-481 |
Improve device logging options |
CME3-502 |
Add information text for readout vs number of meters |
CME3-510 |
Redesign language selector in UI |
CME3-425 |
Spelling error in measurement series template (secundary -> secondary) |
CME3-504 |
Device Logical name in UI is not correct |
Table 155. Implemented changes
ID |
Description |
---|---|
CME3-397 |
Add temperature information in maintenance log |
CME3-419 |
Add CMe3100 temperature as measurement series source |
CME3-136 |
Missing timeframe for expiry time at measurement series |
CME3-278 |
FTP timeout field is missing in the web interface |
CME3-369 |
M-Bus parser error |
CME3-441 |
Stream mode floods log |
Table 156. Implemented changes
ID |
Description |
---|---|
CME3-411 |
Sending nke=253 when experiencing M-Bus decoding errors |
Table 157. Implemented changes
ID |
Description |
---|---|
CME3-133 |
New logotypes for meter manufacturers added |
CME3-387 |
CMe3100 is now able to handle intermittent error in Badger Water Meter E-Series not getting selected/deselected during search/readout. Feature may be enabled/disabled using configuration. See new configuration parameters device.mbus.nke.*. |
CME3-396 |
A new connection is now established for each new DLMS Push Report |
CME3-235 |
Help text of default e-mail sender address is not correct |
CME3-353 |
FTP timeout field is missing in the web interface |
CME3-356 |
Setting a recurrent reboot via cron does not work |
CME3-389 |
REST call may result in the memory getting full |
Table 158. Implemented changes
ID |
Description |
---|---|
CME3-335 |
Cron is not updated when syncing settings (auto configuration) |
CME3-337 |
Swedish translation on the web server configuration page (Configuration/Services/Webserver) is wrong |
Table 159. Implemented changes
ID |
Description |
---|---|
CME3-334 |
DLMS did not handle increasing frame counters correctly when DLMS clients performed pull requests. |
Table 160. Implemented changes
ID |
Description |
---|---|
CME3-294 |
Fraud log events in DLMS plugin are now divided. One report for gateway events and one report per meter for meter events. In previous versions they were all sent in one report. |
CME3-314 |
Column ‘logid’ for log event added when exporting logs. |
CME3-315 |
Column ‘created’ extended to show also milliseconds of the log event when exporting logs. |
Table 161. Implemented changes
ID |
Description |
---|---|
CME3-237 |
DLMS plugin user interface improvements: OBIS codes are now configurable |
CME3-268 |
Added two new type of Report Templates (e-mail, FTP and HTTP) |
Table 162. Implemented changes
ID |
Description |
---|---|
CME3-234 |
Added possibility to set runbefore commands in web interface |
CME3-160 |
Advanced meter search made more user-friendly |
CME3-231 |
Some types of meters are not reacting to storevalue commands from CMe3100 |
CME3-230 |
Some types of meters cannot be installed by CMe3100 |
CME3-198 |
When auto configuration has been started, it cannot be disabled |
CME3-138 |
Temporary folders are not deleted at reboots |
Table 163. Implemented changes
ID |
Description |
---|---|
CME3-205 |
Meter installation is interrupted due to collisions on the M-Bus line |
Table 164. Implemented changes
ID |
Description |
---|---|
CME3-210 |
In cases when CMe3100 does not receive a 2xx response from the HTTP server, Push Reports will not be sent |
CME3-163 |
An error in the product third-party library prevents secure DLMS Push Reports from being sent |
CME3-162 |
The DLMS plugin does not handle some integers correctly |
Table 165. Implemented changes
ID |
Description |
---|---|
CME3-111 |
Users are now able to export raw M-Bus data via the REST interface |
CME3-125 |
“REST: UserLink – Delete userlink (s)” returns failure message when the operation is successful |
CME3-124 |
Some REST features generate incorrect response messages |
CME3-113 |
DLMS: Secured push is not according to standard |
CME3-112 |
Unable to add or edit content in the user.cfg configuration file via REST |
CME3-102 |
Device fails to upload data via FTPS in some cases |
CME3-26 |
Device accepts uploads of software file formats that it is unable to handle |
Table 166. Implemented changes
ID |
Description |
---|---|
CME3-79 |
Existing meter icons have been improved |
CME3-61 |
Change log has been replaced by a link to the corresponding information on the website |
CME3-14 |
Missing meter icons have been implemented in the CMe3100 web interface |
CME3-92 |
The time of the device cannot be set manually |
CME3-91 |
An old user’s manual reference has not been removed from the web interface |
CME3-90 |
The online resources section links to the old website |
CME3-87 |
Certain URIs are not handled properly |
CME3-12 |
M-Bus telegram is not published in system log when an M-Bus decode exception is caught |
CME3-11 |
Duplicated devices in meter list are ignored |
Table 168. Implemented changes
ID |
Description |
---|---|
4514 |
REST: Delete log is removed to improve security, now also removed from help section |
4491 |
Default time synchronization is changed to 11:30 pm/am instead of 0:30 pm/am |
4055 |
REST: Device can now be updated via identification field (/device/update/identification/{identification}/…) |
4230 |
Meters with compact frame cannot be decrypted (e.g. Kamstrup MC21) |
Table 169. Implemented changes
ID |
Description |
---|---|
4044 |
Measurement series template for gas meters added |
3902 |
License information available in status command |
3739 |
It is now possible to execute auto configuration automatically after it has been saved |
4230 |
Report schedule selection is empty after update |
4063 |
Meter data is read correctly via virtual slave port in continues mode |
3655 |
The option to delete records from the system log via REST interface is removed to improve security |
Table 170. Implemented changes
ID |
Description |
---|---|
4178 |
Virtual M-Bus communication starts with wrong configuration upon reboot |
Table 171. Implemented changes
ID |
Description |
---|---|
4043 |
DLMS does not handle interpunctuation characters as part of octet strings |
Table 172. Implemented changes
ID |
Description |
---|---|
3547 |
New DLMS event "User trying to lower security policy" is added to system lo |
3557 |
Device monitoring is now available using SNMP |
3936 |
Raw and decoded M-Bus data are now available in DLMS |
3950 |
System log event ID is now included in log Push Reports |
3960 |
Certificate handling for HTTPS is improved to allow more advanced setups |
4023 |
Boot counter is now added to device statistics (Device > About) |
3686 |
Format specifiers are sometimes not resolved in system log entry texts |
3843 |
Push Report number is wrong in system log entry text for configuration change events |
Table 173. Implemented changes
ID |
Description |
---|---|
3981 |
Software package update to support improved production process |
Table 174. Implemented changes
ID |
Description |
---|---|
2537 |
HTTP Push Report is logged as failed if receiving web server does not respond with a body |
3844 |
Save & Send test report does not work if security level 1 password is set |
3849 |
Unable to use individual settings for Authentication mode in HTTP Push Reports, default settings are always used |
Table 175. Implemented changes
ID |
Description |
---|---|
3499 |
Mass deployment of firmware updates, configurations and licenses is now possible using the EDM tool |
3539 |
Measurement serie templates can now be imported and exported to simplify configuration |
3566 |
REST interface is now supporting Continuous read out mode using mdmdata/api/single/ or mdmdata/api/multi/ |
3570 |
Modbus slave address can now be changed (Modbus add-on) |
3657 |
Limit for exporting measurement series is now increased to 5000 |
3658 |
"Signal Strength" is now added to measurement series template "Electricity, ABB, general" |
3410 |
Push Reports does not work if schedule is set to daily reports |
3467 |
Meter readout cycle is aborted if a wireless meter is faulty |
3560 |
Heavy load on Virtual M-Bus over TCP/IP sometimes causes "Error connecting." |
3561 |
Scheduling a Push Report with a shorter interval than it takes to complete the report sending causes the device to become overloaded and reboot. |
3564 |
Display error value in settings for Measurement series does not work |
3567 |
Unable to detect a lost Ethernet connection |
3669 |
Sending value or log Push Report causes report service to hang if reports are larger than 100 values per meter / entries (v1.6.0) |
3700 |
Factory reset change the hostname to CMe3100-0016000000 |
3703 |
The M-Bus interface sometimes hangs if multiple services access the M-Bus |
3727 |
DLMS connection idle timeout setting does not work |
3766 |
"filter.device.includelist" setting does not work with Report Templates containing multiple meters in a single file |
Table 176. Implemented changes
ID |
Description |
---|---|
3293 |
Database performance is improved |
3433 |
Automatic retransmit of Push Reports that has failed to reach its destination is now improved |
3435 |
System log is reworked with a complete new set of entries |
3466 |
Option to recover password via e-mail on My Account page is removed to improve security |
3474 |
New feature "DLMS Plugin" is added to list of available add-ons |
3488 |
Link-local address for USB network interface is changed from 192.168.100.1 to 169.254.254.1 to avoid conflicting IP addresses |
3490 |
New feature "Continuous readout mode" |
3497 |
Integration with Kabona systems are now streamlined |
3206 |
Push Report schedule automatically aligns with meter readout schedule |
3175 |
Requesting data through Virtual M-Bus using secondary address sometimes returns wrong/no data |
3195 |
Changing port for the Web server service does not display the "reboot is required" banner |
3276 |
Validation of email address does not allow two dots, e.g. username@mail.co.uk |
3340 |
Push Reports does not handle huge meter values (greater than unsigned int 32) |
3346 |
Unable to decrypt telegrams from CMeX20W, results in error "unknown encryption method" |
3349 |
Add-on settings are not stored when creating a backup file |
3369 |
Meter readout does not show error message when unable to connect to the meter (applies to all versions 1.4.x) |
3482 |
Reports can be malformed if M-Bus field of type string contains non-ascii characters |
3489 |
Unable to search log entries if the search string contains an apostrophe sign (') |
Table 177. Implemented changes
ID |
Description |
---|---|
3427 |
Size of system log increased, and disk cleanup procedure improved |
3428 |
HTTP Push Reports now supports HTTPS |
3426 |
System log is deleted when maximum database size is reached |
3436 |
Columns between "MOID" and "Secondary address" is in wrong order for report template 1112, 2112, 3112 (v1.4.3) |
Table 178. Implemented changes
ID |
Description |
---|---|
3350 |
System security is improved |
3365 |
Client certificates can now be used to authenticate clients connecting to the web server or REST interface (Services - Web server)HTTPS |
3265 |
Unable to download backup file from file repository if larger than 40MB |
3400 |
Manufacturer name is incorrectly shown when importing encryption keys with manufacturer information |
3402 |
An extra tab can be present in the commissioning report |
Table 179. Implemented changes
ID |
Description |
---|---|
3353 |
Upgrading to v1.4.1 when ModBus plugin is installed sometimes causes the ModBus mapping to disappear |
Table 180. Implemented changes
ID |
Description |
---|---|
3292 |
The factory reset function causes database settings to become incorrect. Ref: PQN 22502-5 |
3297 |
The option to delete records from the system log is removed to improve security |
3303 |
Export function in System log can now export the full log as csv (previously limited to 1000 entries) |
Table 181. Implemented changes
ID |
Description |
---|---|
3079 |
Change device is removed to adapt to a coming feature update |
2719 |
Virtual M-Bus can now support enhanced secondary addressing (provided for compatibility reasons) |
3243 |
JavaScript feature in Measurement series is temporarily disabled until a moreuser friendly API has been developed |
3221 |
Measure object ID is added as a separate column to export files from Modbus mappings and file is now filtered according to filter settings on page |
3243 |
JavaScript feature in Measurement series is temporarily disabled until a moreuser friendly API has been developed |
3221 |
Measure object ID is added as a separate column to export files from Modbus mappings and file is now filtered according to filter settings on page |
3170 |
Timeout settings for ftp, http, and email, are added to settings for Services > Push Reports (default is now 60 sec) |
3088 |
Date and time for when device was started is added to the System Panel |
3084 |
Push Report URL is now allowing all types of characters to enable e.g. request parameters |
2917 |
Modbus constant in Measurement series > Modbus Map can now handle decimal constants |
2392 |
Presets for week, month and quarter are added to Report schedule control |
3117 |
New feature "Adaptive Retries" is added to the Push Reports service |
3081 |
Sending Push Reports can hang the report service if receiving HTTP server can't be reached |
2716 |
Sending E-Mail and FTP Push Reports can hang the report service if the receiving server does not manage the connection correctly |
3261 |
Device backup does not store all configuration settings in backup (only meter value database) |
3080 |
System log is flooded with "Connection refused" when using HTTPS to connect to the web interface |
2538 |
Report columns and data is sometimes mismatched if meters are using multi telegram |
3254 |
Device does not warn user if there is not enough disk space to perform a backup which can cause the device to become unresponsive (will need factory reset) |
3253 |
Date & time icon in installation panel is showing a warning when accepted time difference is set to 0 even if time sync is working correctly |
3236 |
Support links are in Swedish when selected language is English |
3201 |
Unable to set Manual DNS if Dynamic IP is chosen |
3193 |
Firmware update dialog is displayed incorrectly in IE 11 |
3175 |
Requesting data through Virtual M-Bus using secondary address sometimes returns wrong data |
3132 |
Virtual M-Bus does not respond with ACK when receiving SND_NKE and using secondary addressing |
3082 |
Unable to set time using Console interface |
3072 |
Editing settings for a faulty meter causes an error page to be displayed |
3071 |
Export file from measurement series table is incorrect |
3007 |
REST interface example about report settings does not work |
3002 |
REST interface GET /system/time sometimes return wrong moth |
2918 |
Changing host name (Network settings) sometimes fails and causes and host name to be reverted to default name |
2749 |
REST interface device command does not work |
2557 |
Sorting meter list on status column sometimes does not work |
2438 |
Changing from static to dynamic IP causes an error if the device has not a working network connection |
Comments (0 comments)