There is a problem with the supply voltage.
Verify 100-240 VAC.
If the problem persists, the product may be malfunctioning.
Error on the M-Bus 2-wire bus.
Verify no short-circuit of the M-Bus bus. The voltage should be between 24-30 VDC.
Verify TCP/IP settings in the internal web interface:
TCP port used for communication
IP address
Ethernet link settings
Verify M-Bus status:
Voltage over M-Bus slave device should be between 24 VDC and 30 VDC.
All M-Bus slave devices must have unique secondary or primary M-Bus addresses depending on addressing mode.
M-Bus slave device baud rates.