Manual administration of meter list in GSM/GPRS M-Bus masters

Password
In order to make changes in the meter list you need to enter the passwords for level 3. Default password is 3333.
 
Clear meter list
To remove all meters from the meter list 3333;database device clear 
 
Delete meter
To delete a meter 3333;database device delete [meter id] 
 
Add meter
To add a meter, you need the following information: addressing type, speed and address (primary or secondary)
 
  • To add a meter with primary address 
    3333;database device add addressingmode=primary baudrate= [speed] primaryaddress=[primary address] secondaryaddress=[secondary address]
  • To add a meter with secondary address
    3333;database device add addressingmode=secondary baudrate=[speed] secondaryaddress=[secondary address]
  • To add a meter with extended addressing 
    3333;database device add addressingmode=esecondary baudrate=[speed] secondaryaddress=[sekundäraddress] fabricationnumber=[extended secondary address] 
Update meter
The settings for a meter can be changed and you can change any number of parameters simultaneously in the same sms. 3333;database device update [meter id] [Parameter1] [Parameter2] 
 
All parameters that can be changed
  • AdressingMode
  • Primary
  • Secondary
  • Esecondary
  • Baudrate 300/2400/4800/9600
  • PrimaryAddress 3 digits, 1-250
  • SecondaryAddress 8 digits
  • Identification8 digits
  • Status Active/Passive
  • FabricationNumber 8 digits
  • FCB Mode On/Off/Auto/
  • TelegramCount 1 digit