Technical specifications
Table 24. Mechanics
Type |
Value |
---|---|
Protection class |
IP20 |
Dimensions |
90 x 65 x 36 mm |
Weight |
85 g |
Connection M-Bus |
Spring terminal |
Cable M-Bus |
Solid wire 0.6-0.8 Ø mm, e.g. EKKX 2x2x0.5 |
Mounting |
DIN mounted |
Connection I/O |
Screw terminal. Use 0.5 Nm tightening torque |
Cable I/O |
Wire 0.75-2.5 mm2, e.g. MK450/750V 1 mm2 |
Table 25. Electrical characteristics
Type |
Value |
---|---|
Power consumption |
1.5 mA M-Bus 1T |
Installation category (OVC) |
CAT II (extend protection with external transient protection if higher OVC) |
Output relay current (max) |
8 A |
Output relay voltage (max) |
240 VAC |
Input loop max resistance |
1 kΩ |
Input type |
Normally open |
Input minimum open/close time for pulse detection |
20 ms |
Table 26. Environmental specifications
Type |
Value |
---|---|
Operating temperature range |
-30 to +55 °C |
Storage temperature range |
-40 °C to +85 °C |
Pollution |
Degree 2 |
Operating altitude |
0-2000 m |
Table 27. M-Bus
Type |
Value |
---|---|
M-Bus standard |
EN 13757 |
M-Bus baud rate |
300, 2400 Bit/s |
M-Bus commands |
SND_UD, SND_NKE, REQ_UD2 |
Addressing modes |
Secondary, primary |
Comments (0 comments)