Technical specifications
Table 245. Mechanics
Type |
Value |
---|---|
Casing material |
ABS UL94-V0 (white) |
Protection class |
IP20 |
Dimensions |
35 x 95 x 65 mm (2 DIN modules) |
Weight |
100 g |
Antenna |
Internal (optionally external via SMA-f) |
Mounting |
Mounted on DIN rail (DIN 50022, 35 mm) |
Table 247. Electrical characteristics
Type |
Value |
---|---|
Nominal voltage |
220-240 VAC +/- 10 % |
Frequency |
50 Hz |
Power consumption (max) |
<2.5 W |
Power consumption (nom) |
<1 W |
Installation category |
CAT3 |
Table 248. Environmental specifications
Type |
Value |
---|---|
Operating temperature range |
-20 to +55 °C |
Operating humidity max |
80 % RH at temperatures up to 31 °C, decreasing linearly to 50 % RH at 40 °C |
Operating altitude |
0-2000 m |
Pollution degree |
Degree 2 |
Usage environment |
lndoors (can be extended with IP67 enclosure for outdoor use) |
Storage temperature range |
-40 to +85 °C |
Table 249. User interface
Type |
Value |
---|---|
Green LED |
Power |
Red LED |
Error |
Orange LED |
Encrypted mode |
Push button |
Configuration /activation |
Table 251. M-Bus slave interface
Type |
Value |
---|---|
M-Bus standard |
EN 13757-4 (communication by T1) |
Frequency |
868.95 MHz |
Addressing modes |
Electricity meter's secondary address |
M-Bus information |
All fields in the first telegram of the electricity meter |
Transmit power |
25 mW |
Transmit interval |
16 s |
Encryption |
Unencrypted (default) or encrypted |
Table 252. Integration
Type |
Value |
---|---|
Meter implementation |
ABB meters with IR interface |
Maximum number connected meters |
1 |