Configuration options
Table 168. All configuration options
Field name (Abbr.) |
Description |
Default value |
Locked device & correct PAK or open device |
Locked device & no PAK |
Downlink |
---|---|---|---|---|---|
Meter ID |
Meter identification number of the meter. Not configurable. |
N/A |
Readable |
Readable |
N/A |
Power mode |
Used to activate/deactivate the module. |
Passive |
Readable / Writeable |
Readable |
N/A |
Message format |
The message format determines the structure and payload of the telegram sent from the module. |
0x05 (Standard) |
Readable / Writeable |
Readable |
Writeable |
EcoMode |
When activated, 11+1 years of battery-life is guaranteed by adapting the transmit interval of the module to current signal conditions. |
On |
Readable / Writeable |
Readable |
Writeable |
Transmit interval |
Sets the number of minutes between each transmission from the module |
60 min |
Readable / Writeable |
Readable |
Writeable |
Date & Time |
Date and time set for the meter. |
N/A |
Readable / Writeable |
Readable |
N/A |
Set Time Relative |
Adjusts the time of the meter relative to the current time. |
N/A |
N/A |
N/A |
Writeable |
Set Absolute Time |
Sets the time of the meter |
N/A |
Writeable |
N/A |
N/A |
Set UTC offset |
Sets the UTC offset of the meter. |
N/A |
Readable / Writeable |
Readable |
Writeable |
Configuration Lock |
Locks the module to prevent unauthorized access. |
Open |
Readable / Writeable |
Readable |
Writeable |
LoRaWAN® settings |
|||||
Device EUI |
Unique module identification number. Not configurable. |
Device-unique 64-bit number |
Readable |
Readable |
N/A |
Activation type |
Sets the way the device joins the LoRaWAN® network. |
OTAA |
Readable / Writeable |
Readable |
Writeable |
Network join |
Displays whether the module has joined the LoRaWAN® network or not. |
N/A |
Readable |
Readable |
N/A |
Join EUI |
Application ID that determines where data ends up. |
0x 94 19 3A 03 07 00 00 01 |
Readable / Writeable |
Readable |
Writeable |
Device address |
32-bit address used by the module to identify itself on the LoRaWAN® network. |
N/A |
Readable / Writeable |
Readable |
Writeable |
Current data rate |
The current data rate used for the module. |
N/A |
Readable |
Readable |
N/A |
Table 169. Downlink commands
Field name |
TLV |
Number of bytes in configuration |
Configuration |
Example |
---|---|---|---|---|
Configuration lock |
0x05 |
0x01 |
0x00 = Locked 0x01 = Open |
0x00050101 (Enables configuration lock) |
Transmit interval |
0x06 |
0x02 |
0xNumber of minutes between transmission (lsByte -> msByte) |
0x0006021E00 (Sets the Tx interval to 30 minutes) |
Message format |
0x07 |
0x01 |
0x05 = Standard 0x06 = Compact 0x07 = JSON 0x08 = Scheduled – daily redundant 0x09 = Scheduled - Extended 0x0A = Combined heat/cooling 0x0B = Simple billing 0x0C = Plausibility check 0x0D = Monitoring |
0x00070106 (Sets the message format to compact) |
EcoMode |
0x0F |
0x01 |
0x00 = Disable EcoMode 0x01 = Enable EcoMode |
0x000F0100 (Disables EcoMode) |
Set Time Relative |
0x13 |
0x04 |
0xNumber of seconds* (lsByte -> msByte) *Negative numbers supported. |
0x0013043C000000 (Adds 60 seconds to the current time) 0x0013043C000080 (Subtracts 60 seconds from the current time) |
UTC offset |
0x17 |
0x02 |
0xNumber of minutes* (lsByte -> msByte) *Negative numbers supported. |
0x17023C00 (Sets the UTC offset to +60 minutes) 0x17023C80 (Sets the UTC offset to -60 minutes) |
Reboot |
0x22 |
0x02 |
0x759E is used to reboot device (note endianness, LSB first). |
0x0022029E75 (Reboots the device) |
CMi4111 has several different message formats.
Table 170. Message formats
Field |
Size |
Description |
---|---|---|
Message format identifier |
1 byte |
0x05 = Standard 0x06 = Compact 0x07 = JSON 0x08 = Scheduled – Daily redundant 0x09 = Scheduled - Extended 0x0A = Combined heat/cooling 0x0B = Simple billing 0x0C = Plausibility check 0x0D = Monitoring |
Table 171. Payload, message format Standard [0x05]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x05 (= Standard) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Volume |
6 bytes |
INT32 |
Volume (m³) 0411xxxxxxxx = xxxxxxxx * 0.00001 m³ 0412xxxxxxxx = xxxxxxxx * 0.0001 m³ 0413xxxxxxxx = xxxxxxxx * 0.001 m³ 0414xxxxxxxx = xxxxxxxx * 0.01 m³ 0415xxxxxxxx = xxxxxxxx * 0.1 m³ 0416xxxxxxxx = xxxxxxxx m³ 0417xxxxxxxx = xxxxxxxx * 10 m³ |
3 |
Power |
4 bytes |
INT16 |
Power (W) 022Axxxx = xxxx,x W 022Bxxxx = xxxx W 022Cxxxx = xxxx * 10 W 022Dxxxx = xxxx * 100 W 022Exxxx = xxxx kW 022Fxxxx = xxxx * 10 kW |
4 |
Flow |
4 bytes |
INT16 |
Flow (m³/h) 023Bxxxx = xxxx * 0.001 m³/h 023Cxxxx = xxxx * 0.01 m³/h 023Dxxxx = xxxx * 0.1 m³/h 023Exxxx = xxxx m³/h 023Fxxxx = xxxx * 10 m³/h |
5 |
Fw temp |
4 bytes |
INT16 |
Forward temperature (°C) 0258xxxx = xxxx * 0.001 °C 0259xxxx = xxxx * 0.01 °C 025Axxxx = xxxx * 0.1 °C 025Bxxxx = xxxx °C |
6 |
Rt temp |
4 bytes |
INT16 |
Return temperature (°C) 025Cxxxx = xxxx * 0.001 °C 025Dxxxx = xxxx * 0.01 °C 025Exxxx = xxxx * 0.1 °C 025Fxxxx = xxxx °C |
7 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
8 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
Table 172. Payload, message format Compact [0x06]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x06 (= Compact) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
3 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
For message format JSON, the data is presented in a plain text format.
Table 173. Fields, message format JSON [0x07]
Field |
Description |
---|---|
Message format identifier |
0x07 (Message format JSON) |
Energy |
Energy consumption |
Unit |
Unit of energy consumption (Wh, kWh, MWh, GWh, J, kJ, MJ or GJ) |
Meter ID |
Identification number of the meter in which the module is mounted. |
Below shows an example of a telegram sent using the JSON message format.
{"E":12345678,"U":"kWh","ID":87654321}
For message scheduled formats, such as Scheduled Daily Redundant Pulse Extended, two types of messages will be transmitted from the module - a clock message and a data message. Scheduled message formats will read the meter on top of the hour, allowing a predictability of the received telegrams. The difference between a clock message and a data message is described in the following table.
Table 174. Clock message and data message
Message |
Time interval |
Description |
---|---|---|
Clock message |
Once per day |
The clock message presents the current time of the meter. It can be used to verify that the clock is correct and has not drifted more than accepted. |
Data message |
Determined by Transmit interval parameter |
The actual meter data collected from the meter. |
The following table contains a detailed description of the payload of the clock message.
Table 175. Payload, clock message
Field |
Size |
Data type |
Description |
---|---|---|---|
Message format identifier |
1 byte |
- |
0xFA (=Clock message) |
Data/Time |
6 bytes |
32 bit binary integer M-Bus type F |
046Dxxxxxx = Valid date/time message 346Dxxxxxx = Invalid date/time message |
The clock message will be transmitted once every day and the data message at least (regulated by transmit interval parameter or EcoMode) once every day. The transmit interval can only be set the values listed in Table 176, “Transmit interval options ”.
Although the meter readout will occur on top-of-the-hour, the data message will not necessarily be transmitted at that exact time. The LoRaWAN® transmission will occur after a random delay of 0-15 minutes to decrease the risk of collisions. The readout for the clock message occurs at a random hour (00:00- 23:00) at a random minute in the 35-45 interval and will be transmitted immediately after the readout.
Note
When using scheduled message formats, the transmit interval cannot not be set to higher than 1440 (24 hours).
Table 176. Transmit interval options
Parameter |
Values |
Unit |
---|---|---|
Transmit interval |
60, 120, 180, 240, 360, 480, 720, 1440 |
Minutes |
The data message of Scheduled mode-daily redundant contains an accumulated daily energy field, which is updated at 24:00 each day. In other words, depending on transmit interval settings and data rate, the field will be included in between 1-24 telegrams per day. This will increase the probability of the value being received. For example, if the transmit interval is set to “2”, the accumulated energy read at 24:00 will be transmitted 12 times during the 24 next coming hours (every 2nd hour).
Table 177. Payload, message format Scheduled – Daily redundant [0x08]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x08 (= Scheduled – daily redundant) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Volume |
6 bytes |
INT32 |
Volume (m3) 0411xxxxxxxx = xxxxxxxx * 0.00001 m³ 0412xxxxxxxx = xxxxxxxx * 0.0001 m³ 0413xxxxxxxx = xxxxxxxx * 0.001 m³ 0414xxxxxxxx = xxxxxxxx * 0.01 m³ 0415xxxxxxxx = xxxxxxxx * 0.1 m³ 0416xxxxxxxx = xxxxxxxx m³ 0417xxxxxxxx = xxxxxxxx * 10 m³ |
3 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
4 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error flags please refer to the meter’s manual |
5 |
Meter date/time |
6 bytes |
INT32 |
Meter date and time (YY-MM-DD HH:MM) 046Dxxxxxxxx Bit 31-28 = Year-high* Bit 27-24 = Month Bit 23-21 = Year-low* Bit 20-16 = Day Bit 15 = Summertime flag** Bit 12-8 = Hour Bit 7 = Error flag*** Bit 6 = Reserved for future use Bit 5-0 = Minute *The year is read by combining the year-high and yearlow field. For example, year-high = 0010 and year-low = 010 => year = 0010010 **0 = standard time, 1= daylight-saving time ***0 = timestamp is valid, 1 = timestamp is not valid |
6 |
Accumulated energy at 24:00 |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ Note: Before a midnight reading has been performed the Function field of the DIF is set to “value during error state” to indicate that the value is not valid. |
The data message of Scheduled mode-Extended contains all the data fields from message format Standard. In addition to these, it also includes the meter date/time to transmit messages on the full hour.
As for all Scheduled message formats, the transmit interval can only be set to values included in Table 176, “Transmit interval options ”.
Table 178. Payload, message formats Scheduled - Extended [0x09]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x09 (= Scheduled – Extended) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Volume |
6 bytes |
INT32 |
Volume (m³) 0411xxxxxxxx = xxxxxxxx * 0.00001 m³ 0412xxxxxxxx = xxxxxxxx * 0.0001 m³ 0413xxxxxxxx = xxxxxxxx * 0.001 m³ 0414xxxxxxxx = xxxxxxxx * 0.01 m³ 0415xxxxxxxx = xxxxxxxx * 0.1 m³ 0416xxxxxxxx = xxxxxxxx m³ 0417xxxxxxxx = xxxxxxxx * 10 m³ |
3 |
Power / Flow / Fw temp / Rt temp |
12 bytes |
INT64 |
Byte 0-2 = DIF/VIF codes, 0x07FFA0 Byte 3 = Scaling of Power/Flow -Bit 6..4 (n), 10n-3 W, n = 0..7 -Bit 2..0 (m), 10m-3 m³/h, m = 0..7 Byte 4-5 = Fw temp (lsByte -> msByte), °C, 2 decimals Byte 6-7 = Rt temp (lsByte -> msByte), °C, 2 decimals Byte 8-9 = Flow (lsByte -> msByte), 10m-6 m³/h Byte 10-11 = Power (lsByte -> msByte), 10n-3 W |
4 |
Meter ID/ Error bits |
11 bytes |
INT64 |
Byte 0-2 = DIF/VIF codes, 0x07FF21 Byte 3-6 = Error bits (lsByte -> msByte) Byte 7-10 = Meter ID (lsByte -> msByte)* *Sent in binary format. |
5 |
Meter date/time |
6 bytes |
INT32 |
Meter date and time (YY-MM-DD HH:MM) 046Dxxxxxxxx Bit 31-28 = Year-high* Bit 27-24 = Month Bit 23-21 = Year-low* Bit 20-16 = Day Bit 15 = Summertime flag** Bit 12-8 = Hour Bit 7 = Error flag*** Bit 6 = Reserved for future use*** Bit 5-0 = Minute *The year is read by combining the year-high and yearlow field. For example, year-high = 0010 and year-low = 010 => year = 0010010 **0 = standard time, 1= daylight-saving time ***0 = timestamp is valid, 1 = timestamp is not valid |
Message format Combined heat/cooling is developed to be used only in meters that measures both heating and cooling energy.
Table 179. Payload, message format Combined heat/cooling [0x0A]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x0A (Combined heat/cooling) |
1 |
Heat energy |
6 bytes |
INT32 |
Heat energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Cooling Energy |
8 bytes |
INT32 |
Cooling energy consumption (MWh, kWh, GJ) 0480FF02xxxxxxxx = xxxxxxxx,xxx Wh 0481FF02xxxxxxxx = xxxxxxxx,xx Wh 0482FF02xxxxxxxx = xxxxxxxx,x Wh 0483FF02xxxxxxxx = xxxxxxxx Wh 0484FF02xxxxxxxx = xxxxxxxx * 10 Wh 0485FF02xxxxxxxx = xxxxxxxx * 100 Wh 0486FF02xxxxxxxx = xxxxxxxx kWh 0487FF02xxxxxxxx = xxxxxxxx * 10 kWh 048EFF02xxxxxxxx = xxxxxxxx MJ 048FFF02xxxxxxxx = xxxxxxxx * 10 MJ Note: Manufacturer-specific code 0x02 is used to indicate secondary energy (i.e. “Cooling energy”) |
3 |
Volume |
6 bytes |
INT32 |
Volume (m³) 0411xxxxxxxx = xxxxxxxx * 0.00001 m³ 0412xxxxxxxx = xxxxxxxx * 0.0001 m³ 0413xxxxxxxx = xxxxxxxx * 0.001 m³ 0414xxxxxxxx = xxxxxxxx * 0.01 m³ 0415xxxxxxxx = xxxxxxxx * 0.1 m³ 0416xxxxxxxx = xxxxxxxx m³ 0417xxxxxxxx = xxxxxxxx * 10 m³ |
4 |
Fw temp |
4 bytes |
INT16 |
Forward temperature (°C) 0258xxxx = xxxx * 0.001 °C 0259xxxx = xxxx * 0.01 °C 025Axxxx = xxxx * 0.1 °C 025Bxxxx = xxxx °C |
5 |
Rt temp |
4 bytes |
INT16 |
Forward temperature (°C) 0258xxxx = xxxx * 0.001 °C 0259xxxx = xxxx * 0.01 °C 025Axxxx = xxxx * 0.1 °C 025Bxxxx = xxxx °C |
6 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
7 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
Table 180. Payload, message format Simple billing [0x0B]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x0B (= Simple billing) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Meter ID |
8 bytes |
INT32 |
Meter ID 0C78xxxxxxxx |
3 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
4 |
Energy in wrong mounting position |
8 bytes |
INT32 |
Energy in wrong mounting position (Wh, J) 0480FF03xxxxxxxx = xxxxxxxx,xxx Wh 0481FF03xxxxxxxx = xxxxxxxx,xx Wh 0482FF03xxxxxxxx = xxxxxxxx,x Wh 0483FF03xxxxxxxx = xxxxxxxx Wh 0484FF03xxxxxxxx = xxxxxxxx * 10 Wh 0485FF03xxxxxxxx = xxxxxxxx * 100 Wh 0486FF03xxxxxxxx = xxxxxxxx kWh 0487FF03xxxxxxxx = xxxxxxxx * 10 kWh 048EFF03xxxxxxxx = xxxxxxxx MJ 048FFF03xxxxxxxx = xxxxxxxx * 10 MJ Note: Manufacturer-specific code 0x03 is used to indicate “Energy in wrong mounting position”. |
5 |
Previous month energy |
7 bytes |
INT32 |
Energy consumption previous month (Wh, J, Cal) B40100xxxxxxxx = xxxxxxxx,xxx Wh B40101xxxxxxxx = xxxxxxxx,xx Wh B40102xxxxxxxx = xxxxxxxx,x Wh B40103xxxxxxxx = xxxxxxxx Wh B40104xxxxxxxx = xxxxxxxx * 10 Wh B40105xxxxxxxx = xxxxxxxx * 100 Wh B40106xxxxxxxx = xxxxxxxx kWh B40107xxxxxxxx = xxxxxxxx * 10 kWh B4010Exxxxxxxx = xxxxxxxx MJ B4010Fxxxxxxxx = xxxxxxxx * 10 MJ Note: Storage number 0x01 is used to indicate the energy consumption for the previous month. |
Table 181. Payload, message format Plausibility check [0x0C]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x0C (= Plausibility check) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
3 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
4 |
Energy when mounted in the wrong position |
8 bytes |
INT32 |
Energy in wrong mounting position (Wh, J) 0480FF03xxxxxxxx = xxxxxxxx,xxx Wh 0481FF03xxxxxxxx = xxxxxxxx,xx Wh 0482FF03xxxxxxxx = xxxxxxxx,x Wh 0483FF03xxxxxxxx = xxxxxxxx Wh 0484FF03xxxxxxxx = xxxxxxxx * 10 Wh 0485FF03xxxxxxxx = xxxxxxxx * 100 Wh 0486FF03xxxxxxxx = xxxxxxxx kWh 0487FF03Xxxxxxxx = xxxxxxxx * 10 kWh 048EFF03xxxxxxxx = xxxxxxxx MJ 048FFF03xxxxxxxx = xxxxxxxx * 10 MJ Note: Manufacturer-specific code 0x03 is used to indicate “Energy in wrong mounting position”. |
5 |
Missing time |
4 bytes |
INT32 |
Missing time (s, min, h, days) 3420xxxxxxxx = xxxxxxxx s 3421xxxxxxxx = xxxxxxxx min 3422xxxxxxxx = xxxxxxxx h 3423xxxxxxxx = xxxxxxxx days Note: “Value during error state” is intentional. |
6 |
Max Fw temp |
4 bytes |
INT16 |
Maximum forward temperature (°C) 1258xxxx = xxxx * 0.001 °C 1259xxxx = xxxx * 0.01 °C 125Axxxx = xxxx * 0.1 °C 125Bxxxx = xxxx °C |
7 |
Max Rt temp |
4 bytes |
INT16 |
Maximum return temperature (°C) 125Cxxxx = xxxx * 0.001 °C 125Dxxxx = xxxx * 0.01 °C 125Exxxx = xxxx * 0.1 °C 125Fxxxx = xxxx °C |
Table 182. Payload, message format Monitoring [0x0D]
DIB |
Field |
Size |
Data type |
Description |
---|---|---|---|---|
0 |
Message format identifier |
1 byte |
- |
0x0D (= Monitoring) |
1 |
Energy |
6 bytes |
INT32 |
Energy consumption (Wh, J) 0400xxxxxxxx = xxxxxxxx,xxx Wh 0401xxxxxxxx = xxxxxxxx,xx Wh 0402xxxxxxxx = xxxxxxxx,x Wh 0403xxxxxxxx = xxxxxxxx Wh 0404xxxxxxxx = xxxxxxxx * 10 Wh 0405xxxxxxxx = xxxxxxxx * 100 Wh 0406xxxxxxxx = xxxxxxxx kWh 0407xxxxxxxx = xxxxxxxx * 10 kWh 040Exxxxxxxx = xxxxxxxx MJ 040Fxxxxxxxx = xxxxxxxx * 10 MJ |
2 |
Volume |
6 bytes |
INT32 |
Volume (m³) 0411xxxxxxxx = xxxxxxxx * 0.00001 m³ 0412xxxxxxxx = xxxxxxxx * 0.0001 m³ 0413xxxxxxxx = xxxxxxxx * 0.001 m³ 0414xxxxxxxx = xxxxxxxx * 0.01 m³ 0415xxxxxxxx = xxxxxxxx * 0.1 m³ 0416xxxxxxxx = xxxxxxxx m³ 0417xxxxxxxx = xxxxxxxx * 10 m³ |
3 |
Power |
4 bytes |
INT16 |
Power (W) 022Bxxxx = xxxx W 022Cxxxx = xxxx * 10 W 022Dxxxx = xxxx * 100 W 022Exxxx = xxxx kW 022Fxxxx = xxxx * 10 kW |
4 |
Flow |
4 bytes |
INT16 |
Flow (m³/h) 023Bxxxx = xxxx * 0.001 m³/h 023Cxxxx = xxxx * 0.01 m³/h 023Dxxxx = xxxx * 0.1 m³/h 023Exxxx = xxxx m³/h 023Fxxxx = xxxx * 10 m³/h |
5 |
Fw temp |
4 bytes |
INT16 |
Forward temperature (°C) 0258xxxx = xxxx * 0.001 °C 0259xxxx = xxxx * 0.01 °C 025Axxxx = xxxx * 0.1 °C 025Bxxxx = xxxx °C |
6 |
Rt temp |
4 bytes |
INT16 |
Return temperature (°C) 025Cxxxx = xxxx * 0.001 °C 025Dxxxx = xxxx * 0.01 °C 025Exxxx = xxxx * 0.1 °C 025Fxxxx = xxxx °C |
7 |
Meter ID |
6 bytes |
According to M-Bus EN13757-3 identification field |
Meter ID 0C78xxxxxxxx |
8 |
Error bits |
7 bytes |
INT32 |
Error and warning flags 04FD17xxxxxxxx For further information about Error bits please refer to the meter’s manual |
9 |
Energy when mounted in the wrong position |
8-9 bytes |
INT32 |
Energy in wrong mounting position (Wh, J, Cal) 0480FF03xxxxxxxx = xxxxxxxx,xxx Wh 0481FF03xxxxxxxx = xxxxxxxx,xx Wh 0482FF03xxxxxxxx = xxxxxxxx,x Wh 0483FF03xxxxxxxx = xxxxxxxx Wh 0484FF03xxxxxxxx = xxxxxxxx * 10 Wh 0485FF03xxxxxxxx = xxxxxxxx * 100 Wh 0486FF03xxxxxxxx = xxxxxxxx kWh 048EFF03xxxxxxxx = xxxxxxxx MJ 048FFF03xxxxxxxx = xxxxxxxx * 10 MJ 04FB8DFF03xxxxxxxx = xxxxxxxx MCal 04FB8EFF03xxxxxxxx = xxxxxxxx * 10 MCal 04FB8FFF03xxxxxxxx = xxxxxxxx * 100 MCal Note: Manufacturer-specific code 0x03 is used to indicate “Energy in wrong mounting position”. |
Comments (0 comments)