If the problem persists, the product may be malfunctioning.
Red LED is permanently on
Cause
Error on the M-Bus 2-wire bus.
Solution
Verify no short-circuit of the M-Bus bus. The voltage of the bus should be between 21 VDC and 42 VDC.
Cannot read connected M-Bus slaves
Cause
Fault in M-Bus status
Solution
Verify M-Bus status:
Voltage over M-Bus slave device should be between 21 VDC and 42 VDC.
All M-Bus slave devices must have unique secondary or primary M-Bus addresses depending on addressing mode.
M-Bus slave device baud rates.
TX LED is permanently on
Cause
CMeX10 Series is stacked with other CMeX10 Series products and there is a short circuit on a product which is mounted on the left side of the issued product.
Solution
Verify left side mounted products for no short circuit.