Troubleshooting

Product does not respond to M-Bus master

Cause
  • Voltage over M-Bus connector is out of range.

  • The product uses a primary/secondary address that is used by another product.

  • The product and the M-Bus master do not use the same baud rate.

Solution

Verify that:

  • Voltage over M-Bus connector is in the range of 21-42 VDC.

  • The product uses a unique primary/secondary address (depending on addressing mode set).

  • The product and the M-Bus master use the same baud rate.

CMa10 does not display any information

Cause
  • LCD contrast is set too low.

Solution
  • Use the M-Bus command “Set LCD contrast” to configure the value.

    By performing a factory reset, the sensor will return to its original LCD contrast settings.

Temperature value is inaccurate

Cause
  • Incorrect positioning of the product.

Solution

When mounting the sensor, verify that:

  • The product is not mounted near any heat or cold sources.

  • The product is not mounted in direct sunlight.

  • The product is not mounted in a spotlight beam.