Troubleshooting

Product does not respond to M-Bus master

Cause
  • Voltage over M-Bus connector is out of range.

  • The product uses a primary/secondary address that is used by another product.

  • The product and the M-Bus master do not use the same baud rate.

Solution

Verify that:

  • Voltage over M-Bus connector is in the range of 21-42 VDC.

  • The product uses a unique primary/secondary address (depending on addressing mode set).

  • The product and the M-Bus master use the same baud rate.

Temperature value is inaccurate

Cause
  • Incorrect positioning of the product.

Solution

When mounting the sensor, verify that:

  • The product is not mounted near any heat or cold sources.

  • The product is not mounted in direct sunlight.

  • The product is not mounted in a spotlight beam.

Was this article helpful?

0 out of 0 found this helpful
Have more questions? Submit a request

Comments (0 comments)

Article is closed for comments.