Common SMS commands

Symptoms 
There are some important SMS commands for different situations.
 
Purpose
This article describes these commands.
 
Resolution
Commands 
 
If you have any problems or questions, please contact our technical support, support@elvaco.se.

 

Function

Command

Description

Signal strength/
is the terminal working?

status

An answer is sent back with signal strength (1-10). Signal strength 3 is an approved value.

Does GPRS work?

timesync

The terminal communicates via GPRS and sets the clock against an NTP time server.

New installation of meter

install n [profile]

Searches the M-Bus 2-wire bus for n meters secondary and primary. The text ”[profile]” should be replaced with a customer specific profile if customized settings are required. If no profile is set, default settings will be used.

Change of mätare

install n [profile] clean

Searches the M-Bus 2-wire bus for n meters secondary and primary and removes any exchanged meter. The text ”[profile]”  should be replaced with a customer specific profile if customized settings are required. If no profile is set, default settings will be used.

Add meter to existing M-Bus system

install n [profile] keep

Searches the M-Bus 2-wire bus for n new meters secondary and primary and keeps any existing meter. The text ”[profile]”  should be replaced with a customer specific profile if customized settings are required. If no profile is set, default settings will be used.

Send momentary values by e-mail

momreport

Reads momentary values of any existing meter on the M-Bus 2-wire bus and sends the values in an e-mail to a recipient.

Send momentary values to a recipient

momreport
email.to=name@domain.se

Reads momentary values of any existing meter on the M-Bus 2-wire bus and sends the values in an e-mail toname@domain.se.

Collect meter values by sms

Momreport 101 nnnnnnnn

Reads momentary values of the meter with secondary address nnnnnnnn and sends the values in an sms. If there is only one connected meter, the nnnnnn can be left out.

Collect meter values as Excel files

report 1day 1104
email.to=name@domain.se

Reads values of any existing meter on the M-Bus 2-wire bus and sends an e-mail to name@domain.se  with values for the last 24 h in an Excel file.

 

Manually set time

set time="YYYY-MM-DD hh:mm:ss"

Manually sets the time in the module. This can be useful when an NTP server is not accessible.